Reports until 13:29, Friday 02 August 2024
LHO FMCS (PEM)
oli.patane@LIGO.ORG - posted 13:29, Friday 02 August 2024 (79437)
HVAC Fan Vibrometers Check FAMIS

Closes FAMIS#26320, last checked in 79324

Corner Station Fans (attachment1)
- Both MR_FAN2 accelerometers show the fan becoming noisier very erratically starting yesterday (08/01) at ~07:16UTC, so just after midnight Pacific time (attachment2). It looks like accelerometer 2 isn't getting as loud in the last 12 hours as it had been getting before that, but is still jumping around a lot. Accelerometer 1 however, looks like every time it jumps up, it's a bit louder than the previous time. Definitely should be checked out!
- MR_FAN6 1 starter getting a bit noisier 07/31 14:51UTC(attachment3), but it's a consistant noisy, and looking back at last week(attachment4), the noise levels had been similar last week before they were (I assume?) corrected.
- MR_FAN5 2, which had been pretty noisy last week, finally went down in amplitude five days ago
- All other fans are looking normal and within range.

Outbuilding Fans (attachment5)
- All fans are looking normal and within range.

Images attached to this report