In response to recent failures of the air compressor that's holding open some of the gate valves:
There's now a 6-hour trend of the air pressure on the lower left corner of the top screen for nuc28.
If the compressor is working, there should be a saw tooth pattern between 60 and 85 PSI, at 90+ minutes per tooth.
When the pressure drops below 40, the pneumatic gate valves are in danger of closing.
The control room reported visibility issues with the dark color scheme (blue on black). I have changed it to blue on white and thickened the line.
NUC28