Added Pneumatic Gate Valve Alarms to alarms system

If any of the LVEA pneumatic gatevalues were to change their status (OPEN, SOFT-CLOSE, HARD-CLOSE), the alarms system will now send out text and email messages within 2 minutes.

Comments related to this report
david.barker@LIGO.ORG - 12:04, Wednesday 07 August 2024 (79497)

+<!-- Pneumatic Gate Valves -->
+
+<!--
+
+STATUS 07 AUG 2024
+
+     |
+     |
+   (GV6) OPEN
+   [CP1]
+   (GV5) HARD-CLOSE
+     |
+     |
+     |___________(GV7)[CP2](GV8)________
+           SOFT-CLOSE       OPEN
+
+           ANIM PV (hex)
+      OPEN 65280   (0xff00)
+SOFT-CLOSE 4080    (0x0ff0)
+HARD-CLOSE 255     (0x00ff)
+-->
+
+<!-- GV6 -->
+<Channel name="H0:VAC-LY_GV6_ZSM169A_VALVE_ANIM" low="65279" high="65281" description="GV6">
+  <Contact address="5094380826@vtext.com" hot="2" cool="5" description="C:David Barker"></Contact>
+  <Contact address="5094380828@vtext.com" hot="2" cool="5" description="C:Gerardo Moreno"></Contact>
+  <Contact address="5182105653@tmomail.net" hot="2" cool="5" description="C:Jordan Vanosky"></Contact>
+  <Contact address="barker@ligo-wa.caltech.edu"         hot="2"  cool="2" description="E:Dave Barker"></Contact>
+  <Contact address="gmoreno@caltech.edu"                hot="2"  cool="2" description="E:Gerardo Moreno"></Contact>
+  <Contact address="tsadecki@caltech.edu"               hot="2"  cool="2" description="E:Travis Sadecki"></Contact>
+  <Contact address="jvanosky@caltech.edu"               hot="2"  cool="2" description="E:Jordan Vanosky"></Contact>
+  <Contact address="janos@caltech.edu"                  hot="2"  cool="2" description="E:Janos Csizmazia"></Contact>
+</Channel>
+
+<!-- GV5 -->
+<Channel name="H0:VAC-LY_GV5_ZSM159A_VALVE_ANIM" low="254" high="256" description="GV5">
+  <Contact address="5094380826@vtext.com" hot="2" cool="5" description="C:David Barker"></Contact>
+  <Contact address="5094380828@vtext.com" hot="2" cool="5" description="C:Gerardo Moreno"></Contact>
+  <Contact address="5182105653@tmomail.net" hot="2" cool="5" description="C:Jordan Vanosky"></Contact>
+  <Contact address="barker@ligo-wa.caltech.edu"         hot="2"  cool="2" description="E:Dave Barker"></Contact>
+  <Contact address="gmoreno@caltech.edu"                hot="2"  cool="2" description="E:Gerardo Moreno"></Contact>
+  <Contact address="tsadecki@caltech.edu"               hot="2"  cool="2" description="E:Travis Sadecki"></Contact>
+  <Contact address="jvanosky@caltech.edu"               hot="2"  cool="2" description="E:Jordan Vanosky"></Contact>
+  <Contact address="janos@caltech.edu"                  hot="2"  cool="2" description="E:Janos Csizmazia"></Contact>
+</Channel>
+
+<!-- GV7 -->
+<Channel name="H0:VAC-LX_GV7_ZSM179A_VALVE_ANIM" low="4079" high="4081" description="GV7">
+  <Contact address="5094380826@vtext.com" hot="2" cool="5" description="C:David Barker"></Contact>
+  <Contact address="5094380828@vtext.com" hot="2" cool="5" description="C:Gerardo Moreno"></Contact>
+  <Contact address="5182105653@tmomail.net" hot="2" cool="5" description="C:Jordan Vanosky"></Contact>
+  <Contact address="barker@ligo-wa.caltech.edu"         hot="2"  cool="2" description="E:Dave Barker"></Contact>
+  <Contact address="gmoreno@caltech.edu"                hot="2"  cool="2" description="E:Gerardo Moreno"></Contact>
+  <Contact address="tsadecki@caltech.edu"               hot="2"  cool="2" description="E:Travis Sadecki"></Contact>
+  <Contact address="jvanosky@caltech.edu"               hot="2"  cool="2" description="E:Jordan Vanosky"></Contact>
+  <Contact address="janos@caltech.edu"                  hot="2"  cool="2" description="E:Janos Csizmazia"></Contact>
+</Channel>
+
+<!-- GV8 -->
+<Channel name="H0:VAC-LX_GV8_ZSM189A_VALVE_ANIM" low="65279" high="65281" description="GV8">
+  <Contact address="5094380826@vtext.com" hot="2" cool="5" description="C:David Barker"></Contact>
+  <Contact address="5094380828@vtext.com" hot="2" cool="5" description="C:Gerardo Moreno"></Contact>
+  <Contact address="5182105653@tmomail.net" hot="2" cool="5" description="C:Jordan Vanosky"></Contact>
+  <Contact address="barker@ligo-wa.caltech.edu"         hot="2"  cool="2" description="E:Dave Barker"></Contact>
+  <Contact address="gmoreno@caltech.edu"                hot="2"  cool="2" description="E:Gerardo Moreno"></Contact>
+  <Contact address="tsadecki@caltech.edu"               hot="2"  cool="2" description="E:Travis Sadecki"></Contact>
+  <Contact address="jvanosky@caltech.edu"               hot="2"  cool="2" description="E:Jordan Vanosky"></Contact>
+  <Contact address="janos@caltech.edu"                  hot="2"  cool="2" description="E:Janos Csizmazia"></Contact>
+</Channel>
+