The new compressor runs at a higher pressure so the alarms needed to move with that. I changed the minor and major high alarms for H0:VAC-MR_INSTAIR_PT199_PRESS_PSIG for 127 and 130 respectively in epics via the vacuum computer in the back of the control room. These alarm levels cannot be changed outside of the vacuum network. I did not see this channel in the VAC SDF.
Patrick will check if these values are hard coded into Beckhoff and will adjust accordingly.
Currently the slow-controls SDF is not able to monitor non-VAL fields (e.g. alarm fields). Future release will have this feature.