Reports until 16:44, Thursday 15 August 2024
H1 CDS
david.barker@LIGO.ORG - posted 16:44, Thursday 15 August 2024 - last comment - 10:48, Friday 16 August 2024(79561)
Corner Station Dolphin Glitch, h1omc0 fail

We had a failure of h1omc0 at 16:37:24 PDT which precipitated a Dolphin crash of the usual corner station system.

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 17:02, Thursday 15 August 2024 (79562)

System recovered by:

Fencing h1omc0 from Dolphin

Complete power cycle of h1omc0 (front end computer and IO Chassis)

Bypass SWWD for BSC1,2,3 and HAM2,3,4,5,6

Restart all models on h1susb123, h1sush2a, h1sush34 and h1sush56

Reset all SWWDs for these chambers

Recover SUS models following restart.

david.barker@LIGO.ORG - 17:04, Thursday 15 August 2024 (79563)

Cause of h1omc0 crash: Low Noise ADC Channel Hop

oli.patane@LIGO.ORG - 17:18, Thursday 15 August 2024 (79564)OpsInfo

Right as this happened, LSC-CPSFF got much noisier, but there was not any motion seen by peakmon or HAM2 GND-STS in Z direction(ndscope). After everything was back up, it was still noisy. Probably nothing weird but still wanted to mention it.

Also, I put the IMC in OFFLINE for the night since it decided to now have trouble locking and was showing a bunch fringes. Tagging Ops aka tomorrow morning's me

Images attached to this comment
david.barker@LIGO.ORG - 08:20, Friday 16 August 2024 (79567)

FRS31855 Opened for this issue

LOGS:

2024-08-15T16:37:24-07:00 h1omc0.cds.ligo-wa.caltech.edu kernel: [11098181.717510] rts_cpu_isolator: LIGO code is done, calling regular shutdown code
2024-08-15T16:37:24-07:00 h1omc0.cds.ligo-wa.caltech.edu kernel: [11098181.718821] h1iopomc0: ERROR - A channel hop error has been detected, waiting for an exit signal.
2024-08-15T16:37:25-07:00 h1omc0.cds.ligo-wa.caltech.edu kernel: [11098181.817798] h1omcpi: ERROR - An ADC timeout error has been detected, waiting for an exit signal.
2024-08-15T16:37:25-07:00 h1omc0.cds.ligo-wa.caltech.edu kernel: [11098181.817971] h1omc: ERROR - An ADC timeout error has been detected, waiting for an exit signal.
2024-08-15T16:37:25-07:00 h1omc0.cds.ligo-wa.caltech.edu rts_awgtpman_exec[28137]: aIOP cycle timeout
 

david.barker@LIGO.ORG - 10:48, Friday 16 August 2024 (79572)

Reboot/Restart Log:

Thu15Aug2024
LOC TIME HOSTNAME     MODEL/REBOOT
16:49:17 h1omc0       ***REBOOT***
16:50:45 h1omc0       h1iopomc0   
16:50:58 h1omc0       h1omc       
16:51:11 h1omc0       h1omcpi     
16:53:56 h1sush2a     h1iopsush2a 
16:53:59 h1susb123    h1iopsusb123
16:54:03 h1sush34     h1iopsush34 
16:54:10 h1sush2a     h1susmc1    
16:54:13 h1susb123    h1susitmy   
16:54:13 h1sush56     h1iopsush56 
16:54:17 h1sush34     h1susmc2    
16:54:24 h1sush2a     h1susmc3    
16:54:27 h1susb123    h1susbs     
16:54:27 h1sush56     h1sussrm    
16:54:31 h1sush34     h1suspr2    
16:54:38 h1sush2a     h1susprm    
16:54:41 h1susb123    h1susitmx   
16:54:41 h1sush56     h1sussr3    
16:54:45 h1sush34     h1sussr2    
16:54:52 h1sush2a     h1suspr3    
16:54:55 h1susb123    h1susitmpi  
16:54:55 h1sush56     h1susifoout 
16:55:09 h1sush56     h1sussqzout