Sat CP1 Fill

Sat Aug 24 08:13:53 2024 INFO: Fill completed in 13min 49secs

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 08:38, Saturday 24 August 2024 (79681)

TCmins were -159C for today's fill, the outside temp is down to 13C (56F). I've increased the trip temps from full-summer (-140C) to late-summer (-130C). We typically run at this level until mid October.