Reports until 11:13, Thursday 29 August 2024
H1 CDS
david.barker@LIGO.ORG - posted 11:13, Thursday 29 August 2024 (79791)
Alarms reconfigured

A few changes to the CDS cell phone alarm system:

Adding the CDS HW channel caused the alarm system to go unstable (sorry for all the restart messages this caused). Problem was due to the CDS IOC not supporting the VAL, STAT and SEVR fields. The alarm code permits a bypass of these checks with the "fields=0" directive, which I have applied to this channel.