Mon CP1 Fill

Mon Sep 30 08:11:07 2024 INFO: Fill completed in 11min 3secs

Jordan confirmed a good fill curbside.

Because of cold outside temps (8C, 46F) the TCs only just cleared the -130C trip. I have increased the trip temps to -110C, the early-winter setting.