About Last Night: 737 - 1401utc (1237am-701am PDT)
Only looking at locklosses at ISC LOCK states from 500 and above (i.e. with ASC Full IFO); a lot of the other locklosses were at early states (and quite a bit have the FSS Oscillation tag)
- 2024-10-06 07:37:40.716797 UTC (@OBSERVE, see attachement 01)
- No FSS Oscillation tag. Don't see oscilation in Sheila's template.
- However IMC loses lock at same time as ASC-AS
- 2024-10-06 10:09:09.306152 UTC (@OBSERVE, see attachement 02)
- (very similar to above/737utc)
- No FSS Oscillation tag. Don't see oscilation in Sheila's template.
- However IMC loses lock at same time as ASC-AS
- 2024-10-06 11:10:14.523438 UTC (@OBSERVE + FSS OSCILLATION tag, see attachement 03 & 03b (zoom in))
- FSS Oscillation tag.
- Also see on Sheila's template that the FSS starts having glitches for 2min before the lockloss
- AND: NPRO takes a jump at the same time as the FSS glitches start.
- IMC loses lock at same time as ASC-AS
- 2024-10-06 14:01:17.718750 UTC (@OBSERVE, see attachement 04)
- No FSS Oscillation tag. Don't see oscilation in Sheila's template.
- However IMC loses lock at same time as ASC-AS