Displaying report 1-1 of 1.
Reports until 14:06, Tuesday 15 October 2024
H1 CDS
david.barker@LIGO.ORG - posted 14:06, Tuesday 15 October 2024 - last comment - 15:34, Tuesday 15 October 2024(80690)
CDS Maintenance Summary: Tuesday 15th October 2024

WP12131 h1tcscs model, add FMs and Voltage slow channels

Daniel, Vicky, Dave:

A new h1tcscs model was installed when h1oaf0 was rebooted this morning. DAQ restart was required, the addition of 51 slow channels.

WP12132 New Dolphin adapter card Firmware.

Keith, Jonathan, Erik, EJ, Tony, Dave:

Downgraded firmware was loaded onto the Dolphin IX-611 adapter cards in h1sush7, h1cdsh8 and h1oaf0. This is to prevent sponteneous PCI level switching which is possibly the cause of some O4 cornerstation Dolphin glitches.

Procedure was:

WP12134 DAQ Restart Script, Restart rts-nds.service

Jonathan, Erik, Dave:

To prevent /run/nds/jobs filling, the scripts to restart the DAQ was modified to restart the rts-nds.service on the nds machines as well as restarting their rts-daqd.services.

This allows systemd to empty the /run/nds/jobs directory, which was over 50% full on h1daqnds1. We tested this as part of this morning's DAQ restart, it worked well.

WP12087 Add VACSTAT gauge PVs to DAQ

Dave:

My first attempt to add the VACSTAT PVs relating to vacuum gauge monitoring failed because the channel names exceeded the DAQ length limit of 54 characters.

I modified the VACSTAT code to drop the _PRESS_TORR from the PT channels names, which allowed these channels to be added to the DAQ.

A new H1EPICS_VACSTAT.ini file was created which added 368 channels to the EDC. DAQ and EDC restart was needed.

The new VACSTAT IOC was restarted, and the new MEDMs installed into production.

WP12143 Replace failed SDD in h1guardian1

Dave, Jonathan, Erik:

cds_report reported a failed disk in h1guardian1's md3 raid at noon today. Jonathan and Erik found a failed 230GB SDD which is part of the root file system on h1guardian1. It was replaced  with a 1TB SSD (the smallest we have), resyning the new disk only took about an hour.

DAQ Restart

Jonathan, Erik, Dave:

We restarted the DAQ for the addition of h1tcscs slow channels and the new VACSTAT EDC channels. EDC was restarted, its channel count increased from 57061 to 57429.

This was the first test of the new restart script, which after doing the round of rts-daqd restarts then restarts rts-nds on the nds machines.

The only problem was a spontaneous retstart of framewriter 1 after it had written about 3 full frames. It came back by itself and has been stable since.

Comments related to this report
david.barker@LIGO.ORG - 15:34, Tuesday 15 October 2024 (80692)

Tue15Oct2024
LOC TIME HOSTNAME     MODEL/REBOOT
08:20:39 h1sush7      ***REBOOT***  <<< Dolphin firmware install
08:22:27 h1sush7      h1iopsush7  
08:22:40 h1sush7      h1susfc1    
08:22:53 h1sush7      h1sussqzin  
08:23:06 h1sush7      h1susauxh7  
08:32:25 h1cdsh8      ***REBOOT*** <<< Dolphin firmware install
08:34:17 h1cdsh8      h1iopcdsh8  
08:34:30 h1cdsh8      h1isiham8   
08:34:43 h1cdsh8      h1susfc2    
08:34:56 h1cdsh8      h1sqzfces   
08:35:09 h1cdsh8      h1susauxh8  
08:35:22 h1cdsh8      h1pemh8     
08:38:04 h1oaf0       ***REBOOT*** <<< Dolphin firmware install
08:39:45 h1oaf0       h1iopoaf0   
08:39:58 h1oaf0       h1pemcs     
08:40:11 h1oaf0       h1tcscs     <<< New h1tcscs model install
08:40:24 h1oaf0       h1susprocpi 
08:40:37 h1oaf0       h1seiproc   
08:40:50 h1oaf0       h1oaf       
08:41:03 h1oaf0       h1calcs     
08:41:16 h1oaf0       h1susproc   
08:41:29 h1oaf0       h1calinj    
08:41:42 h1oaf0       h1bos       


09:04:44 h1daqdc0     [DAQ]   <<< DAQ 0-leg restart
09:04:57 h1daqfw0     [DAQ]
09:04:57 h1daqtw0     [DAQ]
09:04:58 h1daqnds0    [DAQ]
09:05:06 h1daqgds0    [DAQ]


09:05:26 h1susauxb123 h1edc[DAQ] <<< EDC restart for VACSTAT chanels


09:11:01 h1daqdc1     [DAQ] <<< DAQ 1-leg restart
09:11:13 h1daqfw1     [DAQ]
09:11:14 h1daqnds1    [DAQ]
09:11:14 h1daqtw1     [DAQ]
09:11:22 h1daqgds1    [DAQ]
09:15:52 h1daqfw1     [DAQ] <<< Spontaneous restart of FW1 DAQD
 