New version of VACSTAT

Janos, Dave:

VACSTAT version 1.10

Following several recent false positive VACSTAT alarms due to noise in a single gauge (usually BSC3 PT132) we have made a change to the code to mitigate this.

The new alarm logic is:

The alarm system was modified to alert the vacuum team if the channel H1:CDS-VAC_STAT_GLITCH_NUM_GAUGES is 2 or greater.

My cell phone alarm will continue to sound on a single gauge trip, because tripped gauges are latched out from the sytem and we need to reset any false positives to restore the nominal functionality.

The new code was installed Friday afternoon (15:40 01nov2024 PDT).

Design reasoning:

In the event of an in-chamber gas release the local gauge will see a large signal. Gas migration to neighboring chambers will result in smaller signals there. Increasing their trip sensitivities will increase the chance of seeing a multi-chamber event.

 

Comments related to this report
david.barker@LIGO.ORG - 10:28, Saturday 02 November 2024 (81012)

A new enumerated PV has been added, H1:CDS-VAC_STAT_STATE.

It can have the following values

VACSTAT_STATES = {
    "MONITORING": 0,
    "SINGLE": 1,
    "MULTIPLE": 2,
}
 

MONITORING = nominal state.

SINGLE = one chamber has tripped, all the others have been set to their "sensitive" trip settings.

MULTIPLE = number of chambers tripped >= 2, alarms have been sent.