Follow up from Tuesday maintenance: Daniel upgraded the Beckhoff slow controls software to no longer error on a version mismatch for the new timing cards installed in h1susex and h1omc0 (for new LIGO DAC and variable Duo-Tone frequency respectively).
I have changed the CDS HW stat code to no longer check that the EX timing error was solely due to the version mismatch. I also reverted the SYS_TC3_TIMING.adl file, removing the temporary blurb I had put in there explaining the expected EX error.
I took the opportunity to upgrade the timing entry on the CDS Overview to a system block. This will turn RED if there are any timing errors, or MAGENTA is the timing system freezes. Clicking on it opens the timing overview, please see attached.