Wed CP1 Fill, manually cancelled because TC-A did not reach trip temp

Wed Jan 01 10:04:06 2025 ALERT: Fill done (errors) in 4min 3secs

Gerardo manually cancelled the fill after TC-A flattened out at -58C (trip is -60C). The discharge line pressure reached 0.8 PSIG (trip is 1.0).

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 10:15, Wednesday 01 January 2025 (82071)

Trip temp has been raised to -50C for tomorrow's fill.