Displaying report 1-1 of 1.
Reports until 10:25, Saturday 04 January 2025
LHO VE
david.barker@LIGO.ORG - posted 10:25, Saturday 04 January 2025 (82111)
Sat CP1 Fill, manual cancel

Sat Jan 04 10:19:24 2025 ALERT: Fill done (errors) in 19min 20sec

TC-A started high again (+25C) and didn't quite reach the -60C trip, it flatlined at -58C, so I manually cancelled the fill. Discharge line pressure suggests it was a good fill.

OAT (-0.6C, 31F)

Trip has been increased to -50C for tomorrow's fill.

 