WP12248 OMC0 double duotone frequency
Erik, EJ, Jonathan, Dave:
The duotone frequency generated by the LIGO Timing Card in h1omc0's IO Chassis was increased from (960, 961)Hz to (1920, 1921)Hz
The available frequencies are hard-coded in the FPGA code on the timing card. The IOP model can request one of these frequencies, configued by the following line in the CDS params block:
duotone_frequency=1920
All models on h1omc0 were restarted with the new iop model:
Tue04Feb2025
LOC TIME HOSTNAME MODEL/REBOOT
12:24:55 h1omc0 h1iopomc0
12:25:09 h1omc0 h1omc
12:25:23 h1omc0 h1omcpi
An identical change was made at LLO on l1lsc0's Timing Card.
3 day trend of h1iopomc0's duotone zero crossing calculation channel: