Reports until 08:06, Wednesday 05 February 2025
H1 CDS
david.barker@LIGO.ORG - posted 08:06, Wednesday 05 February 2025 - last comment - 08:23, Wednesday 05 February 2025(82647)
CDS Maintenance Summary: Tuesday 4th February 2025

WP12248 OMC0 double duotone frequency

Erik, EJ, Jonathan, Dave:

The duotone frequency generated by the LIGO Timing Card in h1omc0's IO Chassis was increased from (960, 961)Hz to (1920, 1921)Hz

The available frequencies are hard-coded in the FPGA code on the timing card. The IOP model can request one of these frequencies, configued by the following line in the CDS params block:

duotone_frequency=1920

All models on h1omc0 were restarted with the new iop model:

Tue04Feb2025
LOC TIME HOSTNAME     MODEL/REBOOT
12:24:55 h1omc0       h1iopomc0   
12:25:09 h1omc0       h1omc       
12:25:23 h1omc0       h1omcpi     
 

An identical change was made at LLO on l1lsc0's Timing Card.

Comments related to this report
david.barker@LIGO.ORG - 08:23, Wednesday 05 February 2025 (82648)

3 day trend of h1iopomc0's duotone zero crossing calculation channel:

Images attached to this comment