WP12343 opslogin0 upgrade
Erik, Jonathan:
Opslogin0 OS was upgraded from deb11 to deb12. Its nomachine server version was upgraded to 8.16.1 (which enabled the OS upgrade).
WP12284 CP1 stop fill on temperature drop
Janos, Dave:
A new version of cp_overfill_ioc.py was ran today which stopped the fill when the thermocouples recorded a drop in temperature of greater than 60C in 30S. The new IOC has additional channels, which were added to H1EPICS_CP1.ini. A EDC+DAQ restart was required.
WP12352 Update DAQ to recent camera move
Patrick, Jonathan, Dave:
Last week cameras 11-14 (MC1, MC3, PRM, PR3) were moved from hdigivideo1 (old server code) to h1digivideo4 (new server code). This new code has a lot more EPICS channels per camera, and two channels have been removed (_XY, _AUTO). So the the past week these cameras have been missing some of their channels in the DAQ, and I had to run a dummy IOC on opslogin0 to "green up" the EDC for the missing XY,AUTO channels.
Today a new H1EPICS_DIGVIDEO.ini was created to bring the EDC up to date. A EDC+DAQ restart was required.
WP12347 Add new VACSTAT channels to DAQ
Dave:
Following the addition of the X6,Y6 gauges to vacstat yesterday, these were added the H1EPICS_VACSTAT.ini for inclusion to the DAQ. A EDC+DAQ restart was required.
DAQ Restart
Jonathan, Dave:
The DAQ was restarted for new EDC ini files (H1EPICS_[CP1, DIGVIDEO, VACSTAT, CDSMON].ini
The new EDC restart procedure was followed. The only issue was a sponteneous restart of FW1 as it was writing its first full frame.
Procedure:
Tue25Feb2025
LOC TIME HOSTNAME MODEL/REBOOT
13:03:24 h1susauxb123 h1edc[DAQ] <<< EDC with new CP1, DIGVIDEO, VACSTAT, CDSMON
13:04:24 h1daqdc0 [DAQ] <<< 0leg restart
13:04:36 h1daqfw0 [DAQ]
13:04:36 h1daqtw0 [DAQ]
13:04:38 h1daqnds0 [DAQ]
13:04:45 h1daqgds0 [DAQ]
13:10:47 h1daqdc1 [DAQ] <<< 1leg restart
13:10:58 h1daqfw1 [DAQ]
13:10:59 h1daqnds1 [DAQ]
13:10:59 h1daqtw1 [DAQ]
13:11:07 h1daqgds1 [DAQ]
13:11:39 h1daqgds1 [DAQ] <<< GDS1 needed a restart to sync chan database
13:13:50 h1daqfw1 [DAQ] <<< FW1 sponteneous crash