eric.otterman@LIGO.ORG - posted 10:36, Tuesday 04 March 2025 - last comment - 14:55, Tuesday 04 March 2025(83154)
End X Chiller 1 failure
After replacing the chiller pump seal, I switched the lead unit to enable to chiller to run, but it failed on water flow. After troubleshooting the chiller, I found that the wiring harness for the flow switch had been chewed on by an animal. I will see about splicing the damaged wiring back together, but until that is done we are down one chiller at End X.
Comments related to this report
eric.otterman@LIGO.ORG - 14:55, Tuesday 04 March 2025 (83170)
This has been repaired and the chiller is now running.