J. Kissel ECR E1700228 One last thing in prep for PM1 from the simulink model perspective: in addition to the "controls" model that Oli and I prepped yesterday (LHO:83196, LHO:83194), we need to add the HAM-A coil driver voltage monitors, the "VMONs" to the h1susauxh2 model. Currently the HAM12 wiring diagram D0902810-v10 is in conflict, indicating that these VMON channels are to be piped in (1) on page 12 to "IN25-28" of the SUS-C4 AA chassis at U11, (2) on page 14 to "IN25-28" of the SUS-C3 AA chassis at U31 which either way feed into ADC0 of the h1susauxh2 IO chassis/computer. I'm 100% confident that (2) is right, and will redline the drawing. As such, I've populated the new PM1 VMON filters with the ADC0 channels 24-27. See attached screenshots. I've tested that the model compiles successfully on the h1build machine. The updates to the model have been committed to the userapps repo as /opt/rtcds/userapps/release/sus/h1/models/ h1susauxh2.mdl rev 30909. No library parts were used or impacted.