Displaying report 1-1 of 1.
Reports until 10:16, Tuesday 11 March 2025
H1 PEM
marc.pirello@LIGO.ORG - posted 10:16, Tuesday 11 March 2025 - last comment - 14:02, Tuesday 18 March 2025(83294)
BSC1 Temperature Sensor Maintenance

We removed the BSC1 temperature sensor to run some testing in the lab.  Will reinstall next week.

Comments related to this report
marc.pirello@LIGO.ORG - 11:59, Tuesday 11 March 2025 (83301)

After testing in the lab, the sensors are working as designed, outputs are clean.  We reinstalled the BSC1 temperature sensor but left it floating (not attached to BSC1). The BSC3 sensor we isolated from BSC3 with a thermal pad, and the power supply was isolated from the pier it is resting on.  This is an effort to remove ground loops on these systems.  Will revisit next week.

M. Pirello, F. Clara

marc.pirello@LIGO.ORG - 14:02, Tuesday 18 March 2025 (83436)

After review of the data over the week, we saw a marked improvement in temprature information so we reapplied the BSC1 sensor to the chamber along with a thermal pad to maintain electrical ground isolation.  We also isolated the power box for both supplies.

M. Pirello, F. Clara, D. Barker