Displaying report 1-1 of 1.
Reports until 14:55, Thursday 13 March 2025
LHO FMCS
eric.otterman@LIGO.ORG - posted 14:55, Thursday 13 March 2025 (83361)
H2 HVAC sub panel breaker replacement
I replaced the three pole, 25 amp circuit breaker which controls the line voltage for an HVAC circuit in the H2. Voltage output was 490 volts.The previous breaker was damaged by heat caused by a loose connection. 