I set up a test for diagnosing front end to front end communications via 4 separate routes:
1) IPC
2) EPICS read (pull data)
3) EPICS write (push data)
4) EPICS write and read, via a third epics server (push to 3rd server, pull from 3rd server)

The setup has a counter on H1odcmaster, this is sent via temporary IPC to h1ascimc, and then returned back to h1odcmaster via the 4 routes described above. For IPC and epics read operations I get an error flag, which I am reporting. No such thing is available for an epics write operation.

h1odcmaster is currently running at 32k, h1ascimc is running at 2k.

I calculated the following quantities
- DELAY          : round trip delay in sec
- DELAY mean     : averaged DELAY
- DELAY max:     : largest DELAY observed
- JITTER MAX     : largest time interval between updates
- JITTER MIN     : shortest time interval between updates
- JITTER MAX-MIN : = JITTER MAX - JITTER MIN, the peak-to-peak jitter
- JITTER RMS     : root-mean-square of the time interval between updates

Conclusion for now:
- No errors observed in the ~1h this was running
- No jitter on IPCs
- epics read has a faster update rate (~8Hz) than epics write (~2Hz)
- as a result the delay is shorter for epics read
- the jitter MAX-MIN is about 40msec for EPICS access - the RMS jitter is about 4msec

I turned on recording for all the fast return channels over the weekend.

The modifications to h1ascimc and h1odcmaster will be backed out on Monday.





Images attached to this report
Comments related to this report
jeffrey.kissel@LIGO.ORG - 13:56, Sunday 03 November 2013 (8365)CDS, SYS
Here is another snapshot after running for 2 days. No qualitative change.
Images attached to this comment