Reports until 13:46, Monday 07 April 2025
H1 CDS (CDS, ISC, SYS)
jeffrey.kissel@LIGO.ORG - posted 13:46, Monday 07 April 2025 (83777)
Recovery from 2025-04-06 Power Outage: SQZ Timing Comparator Lost Uplink -- Power Cycle Fixes It
J. Kissel, M. Pirello
2025-04-06 Power outage: LHO:83753

Among the things that did not recover nicely from the 2025-04-06 power outage was the Timing Comparator D1001370 that lives in ISC-C2 U40 (see component C261 on pg 3 of D1900511-v9). The symptom was that its time-synchronizing FPGA was caught in a bad state, and the timing fanout in the CER Beckhoff status for the comparator was reporting that H1:SYS-TIMING_C_FO_A_PORT_13_NODE_UPLINKUP was in error (a channel value of zero instead of one). 

We didn't know any of this at the start of the investigation.
At the time of investigation start, we only new of an error by following through the automatically generated "SYS" screens (see attached guide),
   SITEMAP > SYS > Timing > Corner A Button [which had a red status light] 
   > TIMING C_FO_A screen Port 13, dynamically marked as a "C" for comparator [whose number was red, and the status light was red] 
   > Hitting the "C" opens the subscreen for TIMING C_FO_A NODE 13, which shows that red "Uplink Down" message in the middle right
The screenshot shows the NODE 13 screen both in the "now" fixed green version state, and a time-machined "broken" version.

Going out to the CER, we found that status light for Digital Port 13 == Analog Port 14 on the timing fanout (D080534; ISC-C3 U11) was blinking. 
Marc tried moving the comms cable to analog port 16, because "sometimes these things have bad ports." That didn't work, so we moved it back to analog port 14.

That port's comms fiber cable was not labeled, so we followed it physical to find its connection to the SQZ timing comparator (again in ISC-C2 U40, thankfully "right next door"), to find it's "up" status light also blinking.
Marc suggested that the comparators may lose sync, so we power cycled it. This chassis doesn't have a power switch, so we simply disconnected and reconnected its +/-18 V power cable.
After waiting ~2 minutes, all status lights turned green.

#FIXEDIT
Images attached to this report