Reports until 10:43, Wednesday 21 May 2025
H1 CDS
david.barker@LIGO.ORG - posted 10:43, Wednesday 21 May 2025 - last comment - 13:00, Wednesday 21 May 2025(84508)
Fix broken h1susb123 18bit DAC, upgrade all 18bit DACs to 20bit DACs

WP12562

Jonathan, Erik, EJ, Jeff, Ryan, Fil, Dave:

As part of the h1susb123 crash investigation, after power cycling the computer and IO Chassis the next thing to do was to replace the 2nd 18bit-DAC card which was no longer visible on the bus.

During the 08:30 vent meeting it was discussed which option we should pursue: replace the suspect 18bit-DAC with another 18bit-DAC, replace this one card with a 20bit-DAC, replace all six 18bit-DACs with 20bit-DACs. The third option was chosen.

Hardware:

Keep the exisiting two 20bit-DACs, replace the six 18bit-DACs with 20bit-DACs. Put aside the second 18bit-DAC as a suspect card, put the other five cards into the O4 spare pool.

Adnaco-slot A3-4 A3-3 A3-2 A3-1   A2-4 A2-3 A2-2 A2-1   A1-4 A1-3 A1-2 A1-1
was 20bit DAC-1 18bit 101208-60 18bit 101208-09 18bit 110425-20   18bit 110425-48 20bit DAC_0 18bit 110425-23 ADC-1   18bit 110425-32 ADC-0   timing
is now 20bit DAC 20bit  220218-29 20bit 210303-49 20bit 210303-35   20bit 210303-22 20bit DAC 20bit 210303-57 ADC-1   20bit 220218-08 ADC-0   timing

Sofware:

h1iopsusb123:

replace the DAC area with eight 20bit-DACs from CDS_PARTS, card numbers 0-7. The SWWD system already DACKILLs all eight DACs (card_num 0-7) irregardless of which suspension trips, so no change needed.

No change to INI file.

h1susitmx, h1susetmx, h1susbs, h1susitmpi:

See Jeff's alog for model changes. DAC part naming was chosen such that there were no changes to INI files.

 

Comments related to this report
david.barker@LIGO.ORG - 13:00, Wednesday 21 May 2025 (84517)

Wed21May2025
LOC TIME HOSTNAME     MODEL/REBOOT
07:29:37 h1susb123    ***REBOOT*** <<< try power cycle computer
07:32:01 h1susb123    h1iopsusb123
07:51:06 h1susb123    ***REBOOT*** <<< try power cycle computer and IO Chassis
07:53:30 h1susb123    h1iopsusb123
09:53:47 h1susb123    ***REBOOT*** <<< replace all 18bit-DACs with 20bit-DACs
09:56:18 h1susb123    h1iopsusb123
09:56:31 h1susb123    h1susitmy   
09:56:44 h1susb123    h1susbs     
09:56:57 h1susb123    h1susitmx   
09:57:10 h1susb123    h1susitmpi