Displaying report 1-1 of 1.
Reports until 13:57, Friday 30 May 2025
H1 CDS
david.barker@LIGO.ORG - posted 13:57, Friday 30 May 2025 - last comment - 14:10, Friday 30 May 2025(84670)
GC/CDS switch went down, control room lost offset networking

Jonathan, Erik, Dave:

At 12:28 Fri 30may2025 PDT the GC/CDS switch which provides GC networking to the MSR stopped working. Visually the switch looked functional, but it was not providing network services.

Main impact on the control room was:

 . loss of GC/CDS NAT router, no offsite access; DARM FOM stopped (unable to get references), loss of teamspeak

 . loss of all VOIP phones (they were still getting POE power, but reporting no network service).

On Jonathan's suggestion we power cycled the MSR switch. After a very long startup boot (~8 minutes) all services were recovered.

Down time was 12:28 - 12:58 PDT

DARM FOM was restarted.

This switch is called sw-osb165-msr-0. It is in rack MSR-02 U40. It is a Ruckus ICX 7850-482P (48 port, POE, 2 power supplies).

Attached photos show front and rear of the switch. To power cycle, both rear power cords need to be pulled out, orange=UPS black=FAC (note they have locking brackets which need to be disengaged). Power cords are circled in the photo.

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 14:10, Friday 30 May 2025 (84673)
Displaying report 1-1 of 1.