WP 12577 I tried unsuccessfully to use the PowerShell scripts to generate the new h0vaclx TwinCAT 3 solution that adds the BCG552 gauge to HAM1. We are reverting back to using the voltage readout into the ADC on h0vacly. I think the most viable path forward may be to install Visual Studio 2019 onto h0vaclx or see if we can use the TwinCAT remote manager to configure and control the PLC on h0vaclx from another machine. If the second option can work, then I think it may be the best. This was done on h0vaclx: Updated WinSCP to 6.5.3. Downloaded and copied the Inficon Trigon BCG552 EtherCAT ESI-File to C:\TwinCAT\3.1\Config\Io\EtherCAT. Tried and failed to generate a TwinCAT 3 solution from the new PowerShell scripts. Exported the current version of the library code in git to PLCopenXML and imported it into a new Visual Studio 2010 solution on h0vaclx. Built the solution, saved it as a library, and installed the library file into the TwinCAT 3 Library Repository on h0vaclx as version 2.0 (version 1.0 is being used in production) Tried and failed again to generate a TwinCAT 3 solution from the new PowerShell scripts.