Displaying report 1-1 of 1.
Reports until 22:23, Thursday 05 June 2025
LHO VE (VE)
gerardo.moreno@LIGO.ORG - posted 22:23, Thursday 05 June 2025 - last comment - 10:45, Tuesday 10 June 2025(84846)
CP7 Liquid Level Control Valve (LLCV) is Railing (Known Issue)

I noticed that the LLCV is railing at its top value, 100% open, it can't open no more.  This is a known issue, but it appears as if the valve is reaching 100% sooner than expected, meaning when the tank is almost half full.  First, I'm going to try a re-zero the LLCV actuator and await for the results.  First attachment is a 2 day plot of LLCV railing today and yesterday.  The second plot is a 3 year history looking at the tank level and the LLCV, it rails at 100% a few times.

Images attached to this report
Comments related to this report
jon.feicht@LIGO.ORG - 09:59, Friday 06 June 2025 (84856)
BURT restore? PID tuning ok? CP2 @ LLO PID parameters attached for comparison.





Images attached to this comment
gerardo.moreno@LIGO.ORG - 16:19, Friday 06 June 2025 (84873)VE

Thanks Jon.  However, this system has a known issue, it turns out that the liquid level control valve is not suitable for the job, that is the reason why it reaches 100% sooner than later, but it appears as if something slip, now it reaches 100% at a higher level, this is the reason why I want to re-zero the actuator.

Attached is the Fill Control for CP7   The issue was mentioned here for the first time aLOG 4761, but I never found out who discovered this is only briefly mentioned by Kyle. Another entry on aLOG 59841.

Images attached to this comment
gerardo.moreno@LIGO.ORG - 10:45, Tuesday 10 June 2025 (84923)VE

Dirty solution of solving the issue with the LLCV getting railed at 100% open, we used the bypass valve, opened it up by 1/8 of a turn and that did the job.  Not a single shot, but eventually we settle on that turn number.  PID took over and managed to settle around to 92% open for the LLCV.  Today we received a load for the tank for CP7.  We are still going to calibrate the actuator.

Images attached to this comment
Displaying report 1-1 of 1.