RCG 5.5.0 Upgrade

WP12536 RCG5.5.0 Upgrade

WP12624 SWWD variable bypass time h1iopsush2a

WP12625 Fix broken ADC selector h1hpiham4

WP12626 Fix partial ADC MEDM by adding named parts

Jonathan, Erik, EJ, Dave:

Yesterday, Mon 16jun2025, we did the final round of builds and installs of all the models against RCG5.5.0

h1build was rebooted against the new boot server (h1vmboot5-5) and was used to do the builds/installs.

After the builds, I ran each model through check_model_changes and then wrote an output files parser:

check_rcg550_daq_changes.py

All the INI changes were expected, most had the RCG additional channels expected from going from 5.1.4 to 5.5.0.

Exceptions were:

h1iopsusex had 1 less because it was upgrading from 5.3.0 so already had timing card temp chan

The following had additional ADC naming parts:

isibs, isiham3, isiham4, isietmx, isietmy, alsex, alsey, ascimc

Build took about 2 hours. Install took 2hrs 13mins, backing up targets to target_archive took 45GB of disk space, /opt/rtcds is at 89%

Comments related to this report
david.barker@LIGO.ORG - 07:25, Tuesday 17 June 2025 (85114)

Post install, note h1omc0 was already upgraded to 5.5.0 previously