WP12649 Add h1ascimc WFS_B_DC chans to DAQ
Elenna, Dave:
A new h1ascimc model was installed which adds two 16kHz versions of the WFS_B_DC channels to the DAQ. The new channels are
H1:IMC-WFS_B_DC_[PIT,YAW]_OUT_16K_DQ
A DAQ restart was required.
WP12635 VACSTAT HAM1 update
Dave:
A new H1EPICS_VACSTAT.ini was generated. This removes the temporary H1-PT100B VACSTAT gauge and adds the new HAM1 PT100_MOD2 gauge to the DAQ. After the EDC+DAQ restart, VACSTAT was restarted sans H1-PT100B now it is longer needed by EDC.
WP12637 HWS Camera Control
Dave
As part of getting the HWS camera control system running again, its new IOC was added to the EDC via H1EPICS_HWSCAMCTRL.ini. EDC+DAQ restart was needed
DAQ Restart
Dave, Jonathan, Erik
DAQ was restarted for four changes:
1) New H1ASCIMC.ini, adding two new fast DQ channels.
2) New H1EPICS_VACSTAT.ini, removing obsolete VACSTAT chans associated with H1-PT100B
3) Removed H1EPICS_VACHAM1.ini, which was trending the temporary H1 version ot PT100B
4) Added new H1EPICS_HWSCAMCTRL, new HWS camera control's IOC non-string channels.
This was a very messy restart.
After restarting the h1ascimc model, the 0-leg was restarted. A second restart of GDS0 was needed.
After writing two full frames, FW0 crashed and restarted itself.
Once FW0 was back, the 1-leg was restarted. GDS1 needed a second restart.
About 10 minutes later, FW0 had a second crash. This is not unheard of, but very rare.
In the course of investigating it was discovered that FW1 had an unused 1TB Seagate HDD (sda) which has been generating errors over the past month. We decided to remove this from h1daqfw1 since it served no purpose.
Following the DAQ restart, item 2) removal means I can stop running the temporary EPICS IOC vac_ham1_pressure_converter_ioc. This code no longer runs on opslogin0 in a tmux session.
WP12651 Replace h1seih23 IO Chassis +24VDC power supply
Fil, Marc, Erik, Dave:
h1seih23 was fenced and powered down. The IO Chassis was then powered down and its +24VDC supply was replaced (bad fan bearing). System was powered back up with no issues.
Tue01Jul2025
LOC TIME HOSTNAME MODEL/REBOOT
12:30:40 h1asc0 h1ascimc <<< new model
12:33:47 h1daqdc0 [DAQ] <<< 0-leg restart
12:34:00 h1daqfw0 [DAQ]
12:34:00 h1daqtw0 [DAQ]
12:34:01 h1daqnds0 [DAQ]
12:34:08 h1daqgds0 [DAQ]
12:34:12 h1susauxb123 h1edc[DAQ] <<< EDC restart, VACSTAT, H1-PT100B, HWSCAMCTRL
12:35:18 h1daqgds0 [DAQ] <<< 2nd GDS0 restart
12:38:34 h1daqfw0 [DAQ] <<< FW0 First Crash
12:42:18 h1daqdc1 [DAQ] <<< 1-leg restart
12:42:29 h1daqfw1 [DAQ]
12:42:30 h1daqtw1 [DAQ]
12:42:32 h1daqnds1 [DAQ]
12:42:40 h1daqgds1 [DAQ]
12:43:42 h1daqgds1 [DAQ] <<< 2nd GDS1 restart
13:02:52 h1daqfw0 [DAQ] <<< FW0 Second Crash
13:42:22 h1daqfw1 [DAQ] <<< FW1 restarted to remove faulty sda HDD
14:00:38 h1seih23 h1iopseih23 <<< h1seih23 front end power cycle to replace DC power supply
14:00:51 h1seih23 h1hpiham2
14:01:04 h1seih23 h1hpiham3
14:01:17 h1seih23 h1isiham2
14:01:30 h1seih23 h1isiham3
DAQ Changes (NAME, TYPE, RATE)
+ H1:CDS-HWS_CAM_CTRL_ETMX_GPS 4 16
+ H1:CDS-HWS_CAM_CTRL_ETMX_START_GPS 4 16
+ H1:CDS-HWS_CAM_CTRL_ETMX_STATUS 4 16
+ H1:CDS-HWS_CAM_CTRL_ETMX_UPTIME_SEC 4 16
+ H1:CDS-HWS_CAM_CTRL_ETMY_GPS 4 16
+ H1:CDS-HWS_CAM_CTRL_ETMY_START_GPS 4 16
+ H1:CDS-HWS_CAM_CTRL_ETMY_STATUS 4 16
+ H1:CDS-HWS_CAM_CTRL_ETMY_UPTIME_SEC 4 16
+ H1:CDS-HWS_CAM_CTRL_ITMX_GPS 4 16
+ H1:CDS-HWS_CAM_CTRL_ITMX_START_GPS 4 16
+ H1:CDS-HWS_CAM_CTRL_ITMX_STATUS 4 16
+ H1:CDS-HWS_CAM_CTRL_ITMX_UPTIME_SEC 4 16
+ H1:CDS-HWS_CAM_CTRL_ITMY_GPS 4 16
+ H1:CDS-HWS_CAM_CTRL_ITMY_START_GPS 4 16
+ H1:CDS-HWS_CAM_CTRL_ITMY_STATUS 4 16
+ H1:CDS-HWS_CAM_CTRL_ITMY_UPTIME_SEC 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_CONN_VALID 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_ENABLED 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_GLITCH 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_GLITCH_GPS 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_DELTAP_300 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_DELTAP_60 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_DELTAP_600 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_DELTAP_TRIP_300 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_DELTAP_TRIP_60 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_DELTAP_TRIP_600 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_INTERCEPT_300 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_INTERCEPT_60 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_INTERCEPT_600 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_SLOPE_300 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_SLOPE_60 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_SLOPE_600 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_SLOPE_TRIP_300 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_SLOPE_TRIP_60 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_LIVE_SLOPE_TRIP_600 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_OPERATIONAL 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_VALID 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_VALUE 4 16
+ H1:CDS-VAC_STAT_LX_X0_PT100_MOD2_VAL_VALID 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_CONN_VALID 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_ENABLED 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_GLITCH 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_GLITCH_GPS 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_DELTAP_300 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_DELTAP_60 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_DELTAP_600 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_DELTAP_TRIP_300 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_DELTAP_TRIP_60 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_DELTAP_TRIP_600 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_INTERCEPT_300 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_INTERCEPT_60 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_INTERCEPT_600 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_SLOPE_300 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_SLOPE_60 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_SLOPE_600 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_SLOPE_TRIP_300 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_SLOPE_TRIP_60 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_LIVE_SLOPE_TRIP_600 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_OPERATIONAL 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_VALID 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_VALUE 4 16
- H1:CDS-VAC_STAT_LY_X0_PT100B_VAL_VALID 4 16
+ H1:IMC-WFS_B_DC_PIT_OUT_16K_DQ 4 16384
+ H1:IMC-WFS_B_DC_YAW_OUT_16K_DQ 4 16384
- H1:VAC-LY_X0_PT100B_GPS_TIME 4 16
- H1:VAC-LY_X0_PT100B_PRESS_TORR 4 16
- H1:VAC-LY_X0_PT100B_UPTIME 4 16