Jordan V, Anna I
The controller for the HAM3 AIP had maxed out on 7/02/25, so during maintenance today we swapped controllers with a refurbished Minivac controller. The ion pump initially was able to hold pressure and even decrease for a couple hours until it railed again, so this is more likely a failure of the ion pump. See attached plot of pressure after the controller swap.
We will swap the ion pump during next Tuesday maintenance.