Displaying report 1-1 of 1.
Reports until 21:33, Wednesday 16 July 2025
H1 General (Lockloss)
oli.patane@LIGO.ORG - posted 21:33, Wednesday 16 July 2025 - last comment - 08:38, Friday 18 July 2025(85805)
Lockloss

Lockloss at 2025-07-17 04:11 UTC due to a power issue with ETMX and TMSX. Currently in contact with Dave and Fil is on his way in.

ETMX M0 and R0 watchdogs tripped

ETMX and TMSX OSEMs are in FAULT

ETMX ESD off

ETMX HWWD notified that it would trip soon, so SEI_ETMX was preemptively put into ISI_OFFLINE_HEPI_ON to keep ISI from getting messed up when it trips

 

Comments related to this report
david.barker@LIGO.ORG - 21:46, Wednesday 16 July 2025 (85806)

H1SUSETMX ADC channels zeroed out at 21:11:39. SWWDs did not trip because there is no RMS on the OSEM signals, but the HWWD completed its 20 minute countdown and powered down the three ISI coil drivers at 21:32. This indicates ETMX's top stage OSEMs have lost power.

I've opened WP12692 to cover Fil going to EX to investigate.

david.barker@LIGO.ORG - 23:43, Wednesday 16 July 2025 (85807)

During the recovery the +24VDC power supply for the SUS IO Chassis was glitched which stopped all the h1susex and h1susauxex models. To recover I first did a straight forward reboot of h1susauxex (no Dolphin), it came back with no issues.

To reboot h1susex was more involved, remember that the EX Dolphin switch was damaged by the 06 April 2025 power outage and has no network control. The procedure to reboot h1susex I used was:

  • caput H1:IOP-SEIEX_REMOTE_IPC_PAUSE 1
  • caput H1:IOP-ISCEX_REMOTE_IPC_PAUSE 1
  • caput H1:IOP-SUSEX_REMOTE_IPC_PAUSE 1
  • on h1susex:
  • rtcds stop --all
  • sudo systemctl reboot

When h1susex came back, I verified all the IO Chassis cards were present (they were all there)

I unpaused the SEI and ISC IPC by writing a 0 to their IPC_PAUSE channels.

The HWWD came back in nominal state.

I reset the SUS SWWD DACKILLs and unbypassed the SEI SWWD.

DIAG_RESET to clear all the IPC errors (it did so) and clear DAQ CRCs (they cleared).

Handed systems over to control room (Oli and Ryan S).

david.barker@LIGO.ORG - 23:50, Wednesday 16 July 2025 (85808)

From Fil:

-18VDC Power supply had failed and was replaced.

Power supply is in rack VDD-2, location U25-U28, right-hand supply, label [SUS-C1 C2]

old supply (removed) S1202024

new supply (installed) S1300288

 

david.barker@LIGO.ORG - 08:47, Thursday 17 July 2025 (85814)

Last night's HWWD sequence is shown below. Reminder that at +40mins the SUS part of the HWWD trips, which sets bit2 of the STAT. This opens internal relay switches, but since we don't route the SUS drives through the HWWD unit (too noisy) this has no effect on operations. The delay between 22:52 and 23:20 is because h1iopsusex was down between 23:01 and 23:20.

Images attached to this comment
david.barker@LIGO.ORG - 09:23, Thursday 17 July 2025 (85816)
filiberto.clara@LIGO.ORG - 16:34, Thursday 17 July 2025 (85835)

Fan motor seized on failed power supply.

david.barker@LIGO.ORG - 08:38, Friday 18 July 2025 (85844)

Wed16Jul2025
LOC TIME HOSTNAME     MODEL/REBOOT
23:15:13 h1susauxex   h1iopsusauxex
23:15:26 h1susauxex   h1susauxex  
23:20:21 h1susex      h1iopsusex  
23:20:34 h1susex      h1susetmx   
23:20:47 h1susex      h1sustmsx   
23:21:00 h1susex      h1susetmxpi 
 