Displaying report 1-1 of 1.
Reports until 15:28, Tuesday 29 July 2025
H1 CDS
david.barker@LIGO.ORG - posted 15:28, Tuesday 29 July 2025 - last comment - 08:29, Wednesday 30 July 2025(86080)
CDS Maintenance Summary: Tuesday 29th July 2025

WP12709 Replace EX Dolphin IX S600 Switch

Jonathan, Erik, EJ, Dave:

The Dolphin IX switch at EX was damaged by the 06apr2025 power glitch, it continued to function as a switch but its nework interface stopped working. This meant we couldn't fence a particular EX front end from the Dolphin fabric by disabling its switch port via the network interface. Instead we were using the IPC_PAUSE function of the IOP models. Also because the RCG needs to talk over the network to a swich on startup, Erik configured EX frontends to control an unused port on the EY switch.

This morning Erik replaced the broken h1rfmfecex0 with a good spare. The temporary control-EY-switch-because-EX-is-broken change was removed.

Before this work the EX SWWD was bypassed on h1iopseiex and h1cdsrfm was powered down.

During the startup of the new switch, the IOP models for SUS and ISC were time glitched putting them into a DACKILL state. All models on h1susex and h1iscex were restarted to recover from this.

Several minutes later h1susex spontaneously crashed, requiring a reboot. Everything as been stable from this point onwards.

WP12687 Add STANDDOWN EPICS channels to DAQ

Dave:

I added a new H1EPICS_STANDDOWN.ini to the DAQ, it was installed as part of today's DAQ restart.

WP12719 Add two FCES Ion Pumps and One Gauge To Vacuum Controls

Gerardo, Janos, Patrick, Dave

Patrick modifed h0vacly Beckhoff to read out two new FCES Ion Pumps and a new Gauge. 

The new H0EPICS_VACLY.ini was added to the DAQ, requiring a EDC+DAQ retstart.

WP12689 Add SUS SR3/PR3 Fast Channels To DAQ

Jeff, Oli, Brian, Edgard, Dave:

New h1sussr3 and h1suspr3 models (HLTS suspensions) were installed this morning. Each model added two 512Hz fast channels to the DAQ. Renaming of subsystem parts resulted in the renaming of many fast and slow DAQ channels. A summary of the changes:

In sus/common/models three files were changed (svn version numbers shown):

HLTS_MASTER_W_EST.mdl production=r31259 new=32426

SIXOSEM_T_STAGE_MASTER_W_EST.mdl  production=r31287 new=32426

ESTIMATOR_PARTS.mdl production=r31241 new=32426

HLTS_MASTER_W_EST.mdl:

only change is to the DAQ_Channels list, added two chans M1_ADD_[P,Y]_TOTAL

SIXOSEM_T_STAGE_MASTER_W_EST.mdl:

At top level, change the names of the two ESTIMATOR_HXTS_M1_ONLY blocks:

PIT -> EST_P

YAW -> EST_Y

Inside the ADD block:

Add two testpoints P_TOTAL, Y_TOTAL (referenced by HLTS mdl)

ESTIMATOR_PARTS.mdl:

Rename block EST -> FUSION

Rename filtermodule DAMP_EST -> DAMP_FUSION

Rename epicspart DAMP_SIGMON -> OUT_DRIVEMON

Rename testpoint DAMP_SIG -> OUT_DRIVE

DAQ_Channels list changed according to the above renames.

DAQ Changes:

This results in a large number of DAQ changes for SR3 and PR3. For each model:

+496 slow chans, -496 slow chans (rename of 496 channels).

+64 fast chans, -62 fast chans (add 2 chans, rename 62 chans).

DAQ Restart

Jonathan, Dave:

The DAQ was restarted for several changes:

New SR3 and PR3 INI, fast and slow channel renames, addition of 512Hz fast channels.

New H0EPICS_VACLY.ini, adding Ion Pumps and Gauge to EDC.

New H1EPICS_STANDDOWN.ini, adding ifo standdown channels to EDC.

This was a full EDC DAQ restart. Procedure was:

stop TW0 and TW1, then restart EDC

restart DAQ 0-leg

restart DAQ 1-leg

As usual GDS1 needed a second restart, but unusual FW1 spontaneously restarted itself after have ran for 55 minutes, an uncommon late restart.

Jonathan tested new FW2 code which sets the run number in one place and propagates it to the various frame types.

Comments related to this report
david.barker@LIGO.ORG - 08:29, Wednesday 30 July 2025 (86101)

Detailed DAQ changes in attached file

Non-image files attached to this comment
david.barker@LIGO.ORG - 08:20, Wednesday 30 July 2025 (86100)

Tue29Jul2025
LOC TIME HOSTNAME     MODEL/REBOOT
09:02:53 h1susex      h1iopsusex  <<< Restarts following EX Dolphin IXS600 switch replacement
09:02:57 h1iscex      h1iopiscex  
09:03:07 h1susex      h1susetmx   
09:03:11 h1iscex      h1pemex     
09:03:21 h1susex      h1sustmsx   
09:03:25 h1iscex      h1iscex     
09:03:35 h1susex      h1susetmxpi 
09:03:39 h1iscex      h1calex     
09:03:53 h1iscex      h1alsex     


09:11:30 h1susex      h1iopsusex  <<< h1susex crash
09:11:43 h1susex      h1susetmx   
09:11:56 h1susex      h1sustmsx   
09:12:09 h1susex      h1susetmxpi 


12:15:20 h1sush2a     h1suspr3    <<< New models, EST rename and 2 fast chans added
12:16:28 h1sush56     h1sussr3    


12:19:29 h1susauxb123 h1edc[DAQ] <<< EDC for new VAC-LY and STANDDOWN
12:21:00 h1daqdc0     [DAQ] <<< 0-leg
12:21:08 h1daqfw0     [DAQ]
12:21:08 h1daqtw0     [DAQ]
12:21:10 h1daqnds0    [DAQ]
12:21:17 h1daqgds0    [DAQ]
12:24:10 h1daqdc1     [DAQ] <<< 1-leg
12:24:17 h1daqfw1     [DAQ]
12:24:17 h1daqtw1     [DAQ]
12:24:20 h1daqnds1    [DAQ]
12:24:27 h1daqgds1    [DAQ]
12:25:18 h1daqgds1    [DAQ] <<< GDS1 2nd restart


13:19:29 h1daqfw1     [DAQ] <<< spontaneous restart


16:17:57 h1susex      h1iopsusex  <<< Replace TMSX 18bit-DAC
16:18:10 h1susex      h1susetmx   
16:18:23 h1susex      h1sustmsx   
16:18:36 h1susex      h1susetmxpi 
 

Displaying report 1-1 of 1.