WP12814
Jim, Erik, Dave:
I have rev-locked built and installed Jim's new h1hpiham6 model. This is an internal ADC rewiring of 4 channels, no DAQ restart needed. We will restart the model later this morning when Jim completes his chamber side wiring work.
Jim put HEPI HAM6 into a safe state and we installed the new model at 08:40 PDT. No DAQ restart was required, I just had to clear the DAQ CRCs and DIAG_RESET the latched IPCs.
For a check, I was viewing the filter module MEDMs for WITNESS_P1 and 3DL4C_A_X. With the old code the witness was seeing around 700 counts and A_X zero, with the new code this was reversed, as expected.