We've recently been having some issues with SRM tripping during initial alignment and during DRMI acquisition, alog87370 for example. After consulting with Jeff K, I've bumped up the trip thresholds as listed below. This was based off of the last few trips, so hopefully it has enough of a buffer now. Saved in the safe and observe sdfs.
| Old | New | |
| M1 | 150 | 250 |
| M2 | 200 | 350 |
| M3 | 225 | 400 |