FMCSSTAT alarm is for the FCES temperature drop. The heating cycle stopped around 22:15 Wed 26nov2025 and the room temperature has been dropping since.
Richard has asked for a cell phone alarm on FCES VEA temperature. I have added the following alarm:
<Channel name="H0:FMC-FCES_VEA_SPACE_TEMP_DEGF" low="39" high="90" description="FCES VEA Temp">
which texts/emails Richard and Tyler if alarm persists for 10 minutes or more.