Displaying report 1-1 of 1.
Reports until 08:58, Thursday 27 November 2025
H1 CDS
david.barker@LIGO.ORG - posted 08:58, Thursday 27 November 2025 - last comment - 12:16, Thursday 27 November 2025(88265)
FCES VEA temperature drop overnight

FMCSSTAT alarm is for the FCES temperature drop. The heating cycle stopped around 22:15 Wed 26nov2025 and the room temperature has been dropping since.

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 12:16, Thursday 27 November 2025 (88267)

Richard has asked for a cell phone alarm on FCES VEA temperature. I have added the following alarm:

<Channel name="H0:FMC-FCES_VEA_SPACE_TEMP_DEGF" low="39" high="90" description="FCES VEA Temp">
 

which texts/emails Richard and Tyler if alarm persists for 10 minutes or more.

Displaying report 1-1 of 1.