Reports until 10:14, Monday 08 December 2025
H1 AOS
sheila.dwyer@LIGO.ORG - posted 10:14, Monday 08 December 2025 (88414)
psams ramped off for HAM7 vent

Sheila, Filiberto

In prep for HAM7 vent, we ramped off the psams servo and the requested voltage.  This is different since the addition of the psams servo, screenshot shows how to get to the screens to ramp that off. 

first turned off the servo input, then ramp it's gain from 1 to 0 with 30 second ramp.  Then with 100 second ramp turned off the offset for the requested voltage.  This needs to be done for ZM4,5,2. 

We also set the guardians to down in prep for loosing high votlage to the OPO, SHG and PMC. 

We didn't do the pico controllers yet since Marc and Daniel are debugging them. 

Images attached to this report