Reports until 17:27, Tuesday 31 March 2026
H1 CDS
david.barker@LIGO.ORG - posted 17:27, Tuesday 31 March 2026 (89722)
SWWD code verification and MEDM updates

Following the B13, B2H34 and H12 upgrades in Dec 2025 and Jan 2026 today I did a second round of verification that the IOP models were reading the correct ADC channels and that the MEDMs were correct. The IOP models are correct and no changes were needed.

Some MEDMs had white-boxes for the raw ADC counts, which was addressed. The SWWD MEDMs use macro file substitution for the detailed screens, and the differences that now exist between the sites means it is no longer feasible to maintain these files in the cds/common/medm/ area. Today I moved them to cds/h1/medm before making the final updates.

At this time all the MEDMs are correct with the exception of the BS IPC channel for SUS-BS to SEI-BSC2. h1iopsusb2h34 has a simulink copy-paste error, the channel which should be BS_WD_SND but is actually BS_WD_SND1, hence the white-box.

I'm also reminded that during these upgrades we decided to not change the IPC channel names in order to minimize the scope of work, so IPC names containing B123, H2A, H34 still exist. During the next RCG upgrade we will correct the names.

An overview of the SWWDs at both sites can be found in the DCC T2600106