Displaying report 1-1 of 1.
Reports until 17:33, Tuesday 21 April 2026
H1 General (CDS)
filiberto.clara@LIGO.ORG - posted 17:33, Tuesday 21 April 2026 (89968)
EY Safety Interlock System

WP 13194

The EY interlock system was found with both the ALS and PCAL laser enable outputs disabled. Trending the laser enable channels shows channels went offline during upgrades to the H1SEIEY IO Chassis. Both the EK1501-0010 coupler and EL2904 binary output terminals were replaced. The 24V DC power to the Safety Interlock Chassis was moved to a dedicated 24V power supply.

Displaying report 1-1 of 1.