CDS Maintenance Summary: Tuesday 5th May 2026

WP13221 Add BBSS Fast Channels to DAQ

Tom, Oli, Erik, Dave:

18 BBSS_OSEMINF (SUM, X, Y) DQ channels were added to the DAQ, all at 256Hz. DAQ retstart was required.

WP13223 Add PT100A VACSTAT slow channels to DAQ

Dave:

A new H1EPICS_VACSTAT.ini was generated adding PT100A. An EDC+DAQ restart was required.

WP13228 Add FW2 slow channels to DAQ

Erik, Jonathan, Dave:

Puppet was changed to add three channels unique to FW2 (STATE_0, STATE_1, NUM_WRITERS). An EDC+DAQ restart was required.

WP13235 h1sush6 IO Chassis Install

Fil, Dave:

Fil moved the IO Chassis for h1sush6 from its temporary location in an adjacent rack into the SUSH6 rack on the MER. h1sush6 front end was powered down for the duration of this work.

DAQ Restart

Erik, Jonathan, Dave:

The DAQ and EDC were restarted.

FW2 stopped at the time puppet was upgraded due to a file creation race condition.

For the DAQ restart itself, the main issue was two spontaneous restarts of FW1, both after running for 10 minutes but not synced to the writing of the second trend frame files.

 

Comments related to this report
david.barker@LIGO.ORG - 15:21, Tuesday 05 May 2026 (90127)

11:23:13 h1susb2h34   h1suslo12   <<< New model, add DQ chans to DAQ
11:26:44 h1daqgds0    [DAQ] <<< 0-leg restart, susl012, vacstat, fw2 additions
11:26:48 h1daqfw0     [DAQ]
11:26:48 h1daqtw0     [DAQ]
11:26:49 h1daqnds0    [DAQ]
11:27:39 h1susauxb13 h1edc[DAQ] <<< EDC for vacstat, fw2
11:30:49 h1daqdc1     [DAQ] <<< 1-leg restart
11:30:58 h1daqfw1     [DAQ]
11:31:00 h1daqtw1     [DAQ]
11:31:03 h1daqnds1    [DAQ]
11:31:11 h1daqgds1    [DAQ]
11:32:13 h1daqgds1    [DAQ] <<< gds1 needed a restart


11:40:28 h1sush6      ***REBOOT***  <<< Power up after IO Chassis work
11:41:23 h1daqfw1     [DAQ] <<< First FW1 spontaneous restart, suspiciously close to start of sush6
11:41:30 h1sush6      h1iopsush6  
11:41:43 h1sush6      h1susom0    
11:41:56 h1sush6      h1susobs    
11:42:09 h1sush6      h1susam     
11:42:22 h1sush6      h1susomcab  
11:42:35 h1sush6      h1susom1ab  
11:42:48 h1sush6      h1susom2ab  
11:43:01 h1sush6      h1susom3ab  


11:51:41 h1daqfw1     [DAQ] <<< Second FW1 spontaneous restart, roughly +10mins
12:02:32 h1daqfw1     [DAQ] <<< Third FW1 spontaneous restart, again roughly +10mins