The EndX BRS was stuck in a damping loop (I'm assuming caused by the power outage). Usually when this happens increasing the damping thresholds temperately fixes the issue, so we went ahead and did that.
It seems to only be effecting the ETMX BRS, so we left the ETMY one alone
Jim and I increased the damping thresholds from:
H1:ISI-GND_BRS_ETMX_HIGHTHRESHOLD: 2000-->4000
H1:ISI-GND_BRS_ETMX_LOWTHRESHOLD: 800-->2000
It also looks like the ETMX BRS drifted out of range (maybe due to the heater losing power and not returning to the original level?) so I've increased the voltage going to the heating plates and will check back in tomorrow to see if it's been restored