Displaying report 1-1 of 1.
Reports until 17:31, Monday 20 July 2026
H1 OpsInfo (IOO)
jennifer.wright@LIGO.ORG - posted 17:31, Monday 20 July 2026 (91135)
JAC sdf diffs I accepted in SAFE.snap today

The first image is sdf diffs created after we phased the JAC WFS readouts this morning, the next two are cdsFilt banks that have no filters and a gain 1 but need to be on to route signals from the wavefront sensor readout matrixes I_mtrx and Q_mtrx to the normalised channels H1:JAC-WFS_A_I_PIT_NORM, H1:JAC-WFS_A_I_YAW_NORM, H1:JAC-WFS_B_I_PIT_NORM, H1:JAC-WFS_B_I_YAW_NORM. Confusingly, these are not displayed on the standard 'JAC_WFS_Settings' screens so I might have to put them on there so this doesn't happen in future (this is probably some legacy infrastructure I copied over from the IMC_WFS model blocks that we don't really need).

Images attached to this report
Displaying report 1-1 of 1.