JAC sdf housekeeping

Since we were going through sdf revert today I accepted some JAC ASCIMC and LSC model diffs. See first two images.

The next image is some slow controls settings we want to stay constant when the Bekchoff computer restarts. I didn't accept the pole value as I am still making changes to the heater servo this pertains to.

The last picture shows that i unmonitored the input switch, FM1 and FM2 switches on the JAC-L_SERVO filter bank. These are switched on by the guardian when we lock the JAC so we don't want the JAC to unlock when we sdf revert (as happened today before I made this change to the sdf monitor).