EX HEPI Control Panel

WP 13697

To mitigate the HEPI VFD going down during power glitches, a line/load reactor was installed at EX. HEPI was taken offline and breaker was LOTO. AC power to the VFD controller was routed through the load reactor.

Part Number: KDRAA28H2