Reports until 08:23, Friday 24 June 2011
LHO FMCS
john.worden@LIGO.ORG - posted 08:23, Friday 24 June 2011 (975)
Temperatures in LVEA - LOW
Temperatures in the LVEA have fallen dramatically overnight - average temps are ~60F. This is due to a broken wall temperature sensor which was sending back a reading of 256F - as a result the control system has been doing it's best to reduce that one zone temperature.
I have disabled this sensor until it is repaired. Temps should begin to return to normal.