Displaying reports 65581-65600 of 84499.Go to page Start 3276 3277 3278 3279 3280 3281 3282 3283 3284 End
Reports until 17:03, Wednesday 01 July 2015
LHO VE (VE)
gerardo.moreno@LIGO.ORG - posted 17:03, Wednesday 01 July 2015 (19419)
Vacuum Activities @ Y-End

(Kyle, Gerardo)

Y-End station:
Connected and ran leak detector at turbo's exhaust in place of scroll pump, sprayed new, untested, conflats with 20 seconds of audible helium flow.
No leaks detected.
Turbo pump restored to original configuration.
Pump down continues.

Conflats tested: new Inficon gauge for ESD interlock, NEG pump 10" gate valve conflat only, Old TMDS valve + blank on middle port north door, New TMDS valve + elbow + blank on south door, and new blank for the removal of the old type gauge for ESD interlock.

LHO VE
kyle.ryan@LIGO.ORG - posted 16:01, Wednesday 01 July 2015 (19417)
IP11 indicated "RED" state via CDS is "bogus"
Local controller shows correct voltage and current -> The signal wiring for this unit has never been correct since an additional terminal strip box was added to facilitate moving the original ion pump controller rack as required by the placement of the HEPI pump stations -> I'll consult with the EE folks
H1 SEI (SYS)
hugh.radkins@LIGO.ORG - posted 15:57, Wednesday 01 July 2015 (19416)
EndY HEPI Pump Station Pressure Glitches--Daily to the minute and weekly double glitch--Say what!?

I've seen and noted this before.  It has been present since early Feb when the sensors were quieted and the noise dropped enough.

If you look at trends, there is a brief upward spike on all the pressure sensor channels at the EndY HEPI Pump System that occurs everyday at 0329utc +- seconds!.  Additionally, there is a weekly (Sunday) double glitch.  The first glitch of the Sunday double occurs at the same time as the daily and looks similar and a second (slightly different) hits 20minutes later followed by a downward glitch 10 minutes later.  Yes, every day and every Sunday.

The pressure does cause the pressure servo to react--see the CONTROL_VOUT.  The glitch is actually a 40 second climb of the pressure which the servo attempts to counter with a reduction of the drive output.  If the servo was driving the pressure, the sign would be reversed.

The glitches don't show in the position controllers or the inertial out of loop hepi sensors.  The Actuator performance must not be that sensitive to the absolute or differential pressure.  So, this really is not an IFO issue but we should figure out what is causing this.  This is not seen in the other Pump Station's pressures but they may be currently too noisy.

Attached are 2 hour second trends of the daily and weekly glitches.  Posting this here for the record and will open an integration issue.

Anyone else see anything at this time?

Images attached to this report
LHO General
richard.oram@LIGO.ORG - posted 15:34, Wednesday 01 July 2015 - last comment - 10:51, Thursday 02 July 2015(19415)
LLO PSL HPO diode power supplies turned off and locked out

Danny Sellers, LLO Laser Safety Officer, unplugged and locked out the PSL HPO diode box power supplies to prevent the accidental activation of the High Power Oscillator. 

See photo. The appropriate laser safety documentation concerning the operation of the PSL is being reviewed and updated to reflect the implementation of this new administrative/ engineering control

Note: Having the HPO diode box power supplies off does not interfere in the operation of the 35W Front End laser. 

Also note that LHO made the same change today.

Images attached to this report
Comments related to this report
vernon.sandberg@LIGO.ORG - 10:51, Thursday 02 July 2015 (19424)PSL

The adding the capability to lock out the pump diodes for the HPO is an important change in operational configuration and how we operate the sites' PSLs.  For the record, this is the path followed at LHO to investigate the possibility of an engineering control (the physical locking out of power to the pump diodes), the installation of the control , and the communication with our sister site.

1.  Investigation of the way to disable power to the pump diodes and to determine the effect on auxilliary systems, e.g., FE (front-end monitors and coputer controlled interlocks).

LHO WORK PERMIT #5320

Date: Wed Jul 1 11:19:11 PDT 2015

Serial number: 5320

Task leader: Jason Oberling

People performing work: Jason, Rick

Facility: LHO

A lock and tag will not be used.

Period of Activity: 7/1/2015 - 7/1/2015

Area of Activity: H1 PSL, Laser Diode Room

Hazards:

Activity: In light of the event last week at LLO, to avoid accidental turning on of the PSL High Power Oscillator (HPO) we are going to test turning off the HPO diode box power supplies to see if the Front End (FE) still runs. The laser may trip during this test. In discussion with AEI Hanover, who has been talking with NeoLase, we have been told that this should be possible.

2.  Announcement to the community of a change in configuration, email:

Subject: PSL HPO Diode Box Power Supplies Locked Out
Date: Wed, 01 Jul 2015 12:58:38 -0700
From: Jason Oberling <oberling_j@ligo-wa.caltech.edu>
To: lho all <lho-all@ligo-wa.caltech.edu>



FYI for all:

I have turned off, unplugged, and locked out the H1 PSL HPO diode box power supplies.  This is to prevent the accidental turning on of the HPO, and does not interfere with the operation of the 35W Front End laser.  Lockout IDs are 3986 and 3770.  If for some reason access to these power supplies is needed/desired, come see me.

Jason

3.  Communication of change and status to a broader group; in particular, our LLO colleagues:

Subject: H1 PSL HPO diode power supplies turned off and locked out
Date: Wed, 01 Jul 2015 13:04:59 -0700
From: Jason Oberling <oberling_j@ligo-wa.caltech.edu>
To: lsc-psl@ligo.org, Janeen Romie <janeen@ligo-la.caltech.edu>, Richard Oram <roram@ligo-la.caltech.edu>
CC: fred.raab@ligo.org



As the subject says, I have turned off, unplugged and locked out the PSL HPO diode box power supplies to prevent the accidental turning on of the HPO.  Benno reported in this morning's PSL meeting that this should be possible and I have confirmed: having the HPO diode box power supplies off does not interfere in the operation of the 35W Front End laser.  I recommend LLO implement this as soon as they are able.

Jason

 

 

H1 General
nutsinee.kijbunchoo@LIGO.ORG - posted 13:52, Wednesday 01 July 2015 - last comment - 16:19, Wednesday 01 July 2015(19414)
VEAs now Laser Hazard

Don't forget laser goggles!

Comments related to this report
nutsinee.kijbunchoo@LIGO.ORG - 16:19, Wednesday 01 July 2015 (19418)

ALS-X PLL is locked but not ALS-Y. I tried to change the Crystal Frequency just in case I could fix it quickly but after a few try I didn't have any luck. So, I returned the value back to where it was when I found it (-50.3570649 MHz).

H1 General
jeffrey.bartlett@LIGO.ORG - posted 11:28, Wednesday 01 July 2015 (19413)
Storage Dry Box Temp/Hum Data
Posted below are the data from DB1, DB4, and 3IFO-DES-CAB long term storage cabinets. All data are with normal ranges and expected patterns. The dip in RH recorded for 3IFO-DES-CAB starting on 06/23/15 is from the Dewar being filled. Greater pressure in the Dewar meant more flow through the cabinet, resulting in a lower RH. In short, the cabinets are working as expected.     
Non-image files attached to this report
H1 PSL
edmond.merilh@LIGO.ORG - posted 10:27, Wednesday 01 July 2015 (19411)
PSL DBB scans + ISS Scan
Non-image files attached to this report
H1 CDS
david.barker@LIGO.ORG - posted 10:00, Wednesday 01 July 2015 (19410)
CDS model and DAQ restart report, Tuesday 30th June 2015

maintenance day restart log:

model restarts logged for Tue 30/Jun/2015
2015_06_30 11:25 h1iopsush2b
2015_06_30 11:25 h1iopsush56
2015_06_30 11:25 h1susim
2015_06_30 11:25 h1sussrm
2015_06_30 11:26 h1iopsush56
2015_06_30 11:26 h1susomc
2015_06_30 11:26 h1sussr3
2015_06_30 11:26 h1sussrm
2015_06_30 11:28 h1iopsusb123
2015_06_30 11:28 h1susbs
2015_06_30 11:28 h1susitmx
2015_06_30 11:28 h1susitmy
2015_06_30 11:29 h1iopsush2a
2015_06_30 11:29 h1iopsush56
2015_06_30 11:29 h1susmc1
2015_06_30 11:29 h1susmc3
2015_06_30 11:29 h1suspr3
2015_06_30 11:29 h1susprm
2015_06_30 11:47 h1hpiitmy
2015_06_30 11:47 h1iopseib1
2015_06_30 11:47 h1iopsush56
2015_06_30 11:47 h1isiitmy
2015_06_30 11:47 h1susomc
2015_06_30 11:47 h1sussr3
2015_06_30 11:47 h1sussrm
2015_06_30 12:05 h1iopsush56
2015_06_30 12:05 h1susomc
2015_06_30 12:05 h1sussr3
2015_06_30 12:05 h1sussrm
2015_06_30 12:07 h1iopseib2
2015_06_30 12:07 h1isibs
2015_06_30 12:08 h1hpibs
2015_06_30 12:08 h1hpiham1
2015_06_30 12:08 h1hpiitmx
2015_06_30 12:08 h1iopseib3
2015_06_30 12:08 h1iopseih16
2015_06_30 12:08 h1isiitmx
2015_06_30 12:10 h1hpiham2
2015_06_30 12:10 h1hpiham3
2015_06_30 12:10 h1hpiham4
2015_06_30 12:10 h1hpiham5
2015_06_30 12:10 h1hpiham6
2015_06_30 12:10 h1iopseih23
2015_06_30 12:10 h1iopseih45
2015_06_30 12:10 h1iopsush34
2015_06_30 12:10 h1isiham2
2015_06_30 12:10 h1isiham3
2015_06_30 12:10 h1isiham4
2015_06_30 12:10 h1isiham6
2015_06_30 12:10 h1susmc2
2015_06_30 12:10 h1suspr2
2015_06_30 12:10 h1sussr2
2015_06_30 12:12 h1iopasc0
2015_06_30 12:12 h1ioplsc0
2015_06_30 12:12 h1isiham5
2015_06_30 12:12 h1lsc
2015_06_30 12:14 h1ascimc
2015_06_30 12:14 h1asc
2015_06_30 12:14 h1calcs
2015_06_30 12:14 h1iopoaf0
2015_06_30 12:14 h1lscaux
2015_06_30 12:14 h1oaf
2015_06_30 12:14 h1odcmaster
2015_06_30 12:14 h1omc
2015_06_30 12:14 h1pemcs
2015_06_30 12:14 h1susauxasc0
2015_06_30 12:14 h1sushtts
2015_06_30 12:14 h1tcscs
2015_06_30 12:24 h1iopsush56
2015_06_30 12:24 h1sussrm
2015_06_30 12:25 h1iopsush56
2015_06_30 12:25 h1sussrm
2015_06_30 12:26 h1calcs
2015_06_30 12:26 h1susomc
2015_06_30 12:26 h1sussr3
2015_06_30 12:50 h1lsc
2015_06_30 14:02 h1omc
2015_06_30 14:27 h1nds0
2015_06_30 14:28 h1nds0
2015_06_30 14:36 h1fw0
2015_06_30 15:57 h1broadcast0
2015_06_30 15:57 h1dc0
2015_06_30 15:57 h1fw0
2015_06_30 15:57 h1fw1
2015_06_30 15:57 h1nds0
2015_06_30 15:57 h1nds1
2015_06_30 15:58 h1nds0
2015_06_30 16:06 h1fw1
2015_06_30 16:50 h1broadcast0
2015_06_30 16:50 h1dc0
2015_06_30 16:50 h1fw0
2015_06_30 16:50 h1fw1
2015_06_30 16:50 h1nds0
2015_06_30 16:50 h1nds1
2015_06_30 16:55 h1broadcast0
2015_06_30 16:55 h1dc0
2015_06_30 16:55 h1fw0
2015_06_30 16:55 h1fw1
2015_06_30 16:55 h1nds0
2015_06_30 16:55 h1nds1

H1 SEI
hugh.radkins@LIGO.ORG - posted 09:53, Wednesday 01 July 2015 - last comment - 07:19, Thursday 02 July 2015(19409)
LHO SEI STS2 Update

I reported suspisions about the ETF (Stanford) Seismometer that is now wired up as the STS2-A or HAM2 ground sensor.  That was ten days ago and here is another look from earlier this morning.  Pretty much same conclusion:  The ITMY and HAM5 units show very good coherence even though they are separated by 30meters.  The HAM2 & ITMY sensors are just a couple meters apart and they are no showing the coherence they should: and the HAM2 & HAM5 sensors coherence is similarly poor..

While the problem may be cable or setup (level or igloo rubbing) I suspect the unit itself.

BTL: Any word on these instruments from your experiences?

Images attached to this report
Comments related to this report
richard.mittleman@LIGO.ORG - 07:19, Thursday 02 July 2015 (19421)

If you have it insulated and it isn't rubbing, then it is probably the standard STS needs to get fixed problem, and checked that the feet are locked

H1 PSL
edmond.merilh@LIGO.ORG - posted 09:04, Wednesday 01 July 2015 (19408)
PSL Weekly Report - Past 10 day Trends
Images attached to this report
H1 General
nutsinee.kijbunchoo@LIGO.ORG - posted 09:01, Wednesday 01 July 2015 (19407)
Morning Meeting

Morning Meeting

Safety Meeting

Happy Holiday!

H1 CDS (DAQ)
david.barker@LIGO.ORG - posted 17:47, Tuesday 30 June 2015 - last comment - 17:50, Tuesday 30 June 2015(19402)
CDS Maintenance Summary

h1sush56 18bit DAC upgrade

Dave, Jim

We swapped all 5 DAC cards in h1sush56 with the upgraded firmware versions. The DAC cards were moved within the IO Chassis left by 4 slots to distance them from the new DC power board (D1301004). The 4th DAC card failed its autocal. We replaced this card with a new one, and it also failed autocal. We swapped the 4th and 3rd cards to see if this is a card or slot issue, now the 3rd card failed autocal. We put another new card into the 3rd slot and this time the calibration worked, so two cards which fail autocal have been detected.

h1guardian0 reboot

Dave

I rebooted h1guardian0 because its load average had risen into the 30's. This time the load average started around 12 instead of 7 before, so Ganglia was immediately complaining about overloading. It has since risen into the 20's, so rebooting is now short term relief.

h1sush2b reboot

Jim, Dave

h1sush2b had frozen up around 6pm last night. It required a reboot, which we knew would glitch all Dolphin connected computers so it was delayed until today's restarts. When we rebooted it this morning, we then restarted all corner station SUS, SEI and ISC. This in turn performed the autocal of all 18bit DACs which we indended to do today.

PEM ADC DQ channels

Dave

General ADC channels for occassional PEM work are being written to the frame. I set their gains to 0.0 to ensure they compress out in the frame when not in use. I changed SDF accordingly.

h1lsc new filters

The pending filter module change for h1lsc was applied today after the Dolphin glitch. The filter module H1LSC_SRCLFF has a rolloffs fllter,  which moved from the 5th to 10th location within the filter module.

GRB/SN notification code

Dave

This code has crashed when the offsite networking went down. I upgraded h1fescript0 and restarted the code.

Leap Second

Stefan, Greg, Patrick, Jim, Dave

we tested that the CDS systems handled the leap second addition correctly. All systems did so, but surprisingly conlog crashed (Patrick is investigating). Greg confirmed frames and correct. Dave and Jim check NDS clients dtt and dataviewer.

Comments related to this report
david.barker@LIGO.ORG - 17:50, Tuesday 30 June 2015 (19403)

Clocks on control room wall did not show the 23:59:60 second when applying the leap second. Rather they skewed ahead on second over the following two minutes. The one showing local time did this first, so for about a minute the two clocks differed by one second until the UTC clock caught up.

H1 SUS (DetChar, SUS)
sheila.dwyer@LIGO.ORG - posted 17:45, Tuesday 30 June 2015 - last comment - 10:41, Wednesday 01 July 2015(19401)
MC2 M3 LL zero crossing glitches

I sent a small excitation into MC2 M3 LL last night (29/06/2015 22:37 UTC) and again today after the autocalibration was done (7/1/2015 00:35 UTC). 

The attached screenshot shows the voltmon channel, both before and after.  There isn't a clear difference, it seems like there could be a discontinuity at the zero crossing in both cases, but it is not obvious from the time series if things are better or not after the autocalibration.  

Images attached to this report
Comments related to this report
joshua.smith@LIGO.ORG - 10:41, Wednesday 01 July 2015 (19412)DetChar, SUS

Hi Sheila, looks like your autocal did reduce the glitches somewhat between those two times. In the attached file I used the NOISEMON channels in the frames. But you could also watch the FASTIMON channels during injections from on site (thanks TJ). 

Images attached to this comment
H1 AOS
nicolas.smith@LIGO.ORG - posted 17:30, Tuesday 30 June 2015 (19399)
MICH CPS Feedforward

(jim nic)

We've implemented the ISI CPS -> MICH feedforward (MICH freeze). It was a fairly simple process:

We installed the feedforward coefficients that Ryan suggests in his writeup. These could be re-measured to potentially improve the subtraction.

Then we compared the spectrum of the feedfoward signal and the MICH control signal. We saw a relative gain of 188, so this was added to a filter bank in the feedforward path.

We added a 50Hz low pass to the feedforward path so we aren't injecting too much noise.

When the feedforward path is enabled, we have a reduction in the MICH control signal RMS by a factor of 2-3. See attached figure (reference traces are with FF turned off).

The CPS has a 9Hz feature. Jim says it's from HEPI. This is injected into the MICH control signal, but the change to the RMS is insignificant.

Also attached is the settings of the MEDM screens. Several of these are 'hidden' because they have only been autogenerated and not added to the main screens.

Finally, the easy way to turn on and off the feedforward is by setting the channel H1:LSC-CPSFF_GAIN to 0 (off) or 1 (on). It has a 10 second ramp.

Images attached to this report
Non-image files attached to this report
H1 CDS
patrick.thomas@LIGO.ORG - posted 17:09, Tuesday 30 June 2015 - last comment - 17:31, Tuesday 30 June 2015(19395)
Conlog failed on leap second
Jun 30 16:59:59 h1conlog1-master kernel: [12118377.100031] Clock: inserting leap second 23:59:60 UTC
Jun 30 17:00:11 h1conlog1-master conlog: ../conlog.cpp: 301: process_cac_messages: MySQL Exception: Error: Duplicate entry 'H1:ASC-ODC_CHANNEL_OUTMON-1435708800004681820-3' for key 'PRIMARY': Error code: 1062: SQLState: 23000: Exiting.
Jun 30 17:00:12 h1conlog1-master conlog: ../conlog.cpp: 331: process_cas: Exception: boost: mutex lock failed in pthread_mutex_lock: Invalid argument Exiting.
Comments related to this report
patrick.thomas@LIGO.ORG - 17:31, Tuesday 30 June 2015 (19400)
Restarted
H1 SEI
jim.warner@LIGO.ORG - posted 10:35, Tuesday 30 June 2015 - last comment - 08:36, Wednesday 01 July 2015(19378)
HAM3 23hz line coming from MC2

Hugh and I went to HAM3 this morning to see if we could find the cause of the 23 hz line. Finding nothing at the chamber, we decided to start turning stuff off to see if we could get it to go away. Taking the ISI and HEPI down did nothing, but turning the suspension off made the line go away. I then started turning the SUS back on and as soon as I took MC2 to aligned, the 23hz peak showed up. Jeff said that it was likely the sat amplifier needed power cycled, so Hugh is filing an FRS and this is being handed off to Richard. Attached image shows HAM3 GS-13s between 20 and 30 hz. Red is from last night, when everything was on, blue is everything off, green is MC2 aligned (everything else off).  HEPI L4Cs and both SUS also saw the peak.

Images attached to this report
Comments related to this report
jim.warner@LIGO.ORG - 13:42, Tuesday 30 June 2015 (19385)

After all the restarts earlier and Richard power cycling MC2, the line is gone. See attached. Red trace is from 8 hours ago, blue is from a couple minutes.

Images attached to this comment
richard.mittleman@LIGO.ORG - 07:34, Wednesday 01 July 2015 (19405)

Do we know what power cycling does? how often dows this kind of thing happen?

hugh.radkins@LIGO.ORG - 08:36, Wednesday 01 July 2015 (19406)

Richard--The thought/idea is and maybe there is some way we could verify it, that the satellite amplifier goes into oscillation.

Displaying reports 65581-65600 of 84499.Go to page Start 3276 3277 3278 3279 3280 3281 3282 3283 3284 End