Table legs were set into place and leveled. On Monday the table legs will be grouted into place.
H2 SUS FMY's damping loops are no longer stable with the settings I'd confirmed working yesterday. HOWEVER, they are stable if the signs of all the loops are changed (i.e. change H2:SUS-FMY_M!_DAMP gains from negative to positive). I had logged in this morning (~10a ET, 7a PT) to take some transfer functions on ITMY, noticed in passing that H2 SUS FMY's watchdog had tripped and thought "no big deal," something must have glitch and tripped it over night, and left it be. When I had finished ITMY's measurements, I went back to clean up my work and re-damp everything so that seismic could get to work, and noticed (1) FMY's Master switch was off (was on when I glanced at it) (2) FMY's COILOUTF filter's outputs were off I, by-hand, turned the switches back on, and blindly turned on the the damping loops. The slowly but surely became unstable within a few seconds. Totally confused, I flailed about for a bit looking for sign errors etc. Regrettably I didn't BURT capture FMY after yesterday's confirmation that the damping loops were running yesterday. So, I've BURT restored to the snapshot where the loops were confirmed stable last, in ${RTCDSROOT}/userapps/release/sus/h2/burtfiles/fmy/fmy_dampfilter_111004.snap as per Jeff G.'s aLOG 1506. All loop signs are the same as what I expected (and as I had them set to yesterday) -- the only tweak I needed to do was to select the correct filters in the COILOUTF banks, because Jeff G's snapshot was taken before the filter bank upgrade, mentioned here. After this they're still unstable! In trying to figure out what the heck is wrong, I flipped the sign on the DAMP Filter gains from - to +, and they're stable (?!?!). Still investigating ... Richard has to make some changes to the DC powr supplies at 11a PT, so for now I've turned off all digital control to both ITMY and FMY. I'm looking for something electronic (chassis, ADCs, computers, networks, etc.) or digital (MEDM setting, model changes, CDS software changes) that might cause the sign of the actuation to flip -- and only on FMY. It's VERY strange. Perhaps the timing glitch, and Dave's subsequent reboot of everything and BURT restore, mentioned in passing here, changed something digital upstream of the FMY signal chain (like the IOP)? Sounds unlikely, but possible ...
Upgrade of control room and MSR update. Floor tiles were removed, under floor cables are being removed. Timing system in the MSR was glitched, requiring all front ends plus their IO Chassis to be power cycled. All systems were burt restored to 15:00 local time.
Attached are plots of dust counts > .5 microns. The dust monitor in the clean room over BSC8 had a low battery alarm when I came in today, and I restarted it. The system was down intermittently while the servers were moved from the MSR to the electronics building.
Final work on linoleum was completed today. All seams were welded, and grout dams were caulked into place. Table legs were also moved over to the South bay.
(Corey, Hugo, Jim, Mitch)
Assy #3
For all intents and purposes, this Assembly is ready to be pulled off the Test Stand.
Assy #1
T. Sadecki, J. Kissel Travis / Hugh can give more details of the problems had during cabling up the H2SUSFMY, but once we got all BOSEMs turned on, and the OSEMINF filters were fixed, it was trivial to close the damping loops on FMY (as it should be!). All damping loops (ITMY M0, ITMY R0, and FMY M1) are closed and running. Watchdog levels: OSEM DC -- +/- 30000 OSEM AC RMS -- 8000 ACT AC RMS -- 25000 Typical watched levels with damping loops closed (and no one mucking around the chamber) OSEM DC -- ~15000 OSEM AC RMS -- < 150 ACT AC RMS -- < 1000
Crystal chiller flow increased from 14.5 lpm to 15.2 lpm
Diode chiller flow increased from 24 lpm to 28 lpm
Diode chiller pressure at valve underneath table increased from 4.3 bar to 5 bar
J. Batch, J. Kissel After failed attempts to run diagonalization measurements of the newest QUAD built using DTT (DTT opens, sends excitation out to the suspension as seen on MEDM, runs for the allotted time and stops, but no data is plotted and DTT reports an error message say "Test time out."), Jim found that the framebuilder / daqd process had "somehow lost 30 seconds ... possibly because we unplugged a cable temporarily." I think he's referring to timing cables that may have been plugged/unplugged during the Mass Storage Room gutting. He has rebooted the frontend, and I have burt restored using the ${RTCDSROOT}/userapps/release/sus/x1/burtfiles/x1susquad_safe.snap restore file. I'm retaking the diag. measurements now, and all is functioning properly.
While on the phone, but still watching the MEDM screens of SUS's in BSC8, I saw the values coming in off the front end freeze. After some investigation, I found that the IOPs for both front ends that control H2SUSITMY and H2SUSFMY had lost their IRIG-B timing -- H2:FEC-28_IRIGB_TIME, H2:FEC-28_IRIGB_TIME were some large red number (normally green and around ~15 us). This also seems to have caused all the running models on those front ends to have a red 0x4000 status with regards to the framebuilder / daqd. I'm not sure why all this happened, but I've restarted the processes on both front ends and all seems fine...
Work continues on the aLIGO upgrade of the LHO control room and MSR. The iLIGO computing systems have largely been removed, we are now de-cabling both rooms.
EricA CoreyG HughR Re--WorkPermit 3029 We got 3 vertical and 1 horizontal Actuators connected so 1/2 way there. We didn't get started on the actual attachment til 1pm so I think we should be able to wrap it up in the morning. We'll still need to adjust the Springs after all connected but again, maybe we'll be wrapped up early afternoon. As usual, please be mindful of the dial indicators if you are in their neighborhoods.
D. Cook, J. Oberling
We placed 3 new monuments west of BSC06 at End Y today for use in the in-chamber alignment of the H2 ETMy. These are labeled IAM-25, IAM-26, and IAM-27 and their coordinates are as follows (units of mm):
After powering up the FMy satellite boxes and checking that the EE on the outside of the chamber were functioning properly (thanks, Richard), I went in the chamber to look at the in-vacu stuff. Indeed, the cable that needed an end-to-end swap before the holiday break, had not finished making it to it's connecting octopus cable. When I tried to seat it, I found that the 225 cable needed helicoils, preventing good connection. We're hunting tools now to finish helicoiling these (all 3 225 cables need the helicoils) connectors.
Today I finished helicoiling and connecting the FMy cabling at the optical table. While this eliminated a possible source of problems, it turned out the real problem was a bent pin on the air side of the feedthrough. After straightening the bent pin, the cable was reconnected and successfully tested for functionality.
Though there was a bent pin on the Vac. flange I believe this was a result of troubleshooting and not the initial cause. Per my directions this cable was removed and changed and replugged in a number of times in trying to narrow down the problem.
I often use HTML tags in my aLOG entries to change fonts or colors in my entry. Sometimes, I forget to close the tag. This causes the rest of the page of logs below it to inherit the property of the tag I left open. (Others have done this / use HTML tags / caused this error -- I say this only to emphasize that it's not just me; it's beside the point). For example, search the log for my name, and the keyword "/Common/MatlabTools/." This returns several entries (to be sure I demonstrate them getting "infected" by my left-open <font face="courier"> tag). Scroll to entry 1507 (a comment to Jeff Garcia's entry 1506, 5 entries down), and see that all entries below it have their font changed. EVEN MORE CURIOUS: The bug manifests itself differently on different platforms. On a workstation-like machine ( Ubuntu 10.04 LTS, running FireFox 3.6.24), the open tag affects rest of the page in it entirety. On my laptop (Mac OS X 10.7.2, FireFox 8.0.1) it only affects the headers and footers to the entry (Subsystem/Task, Author and Date, and Title; any attachment indicators), the bodies retain their formatting. I usually catch this user error, because I run preview before I post, but sometimes it slips. Regardless, I think the log should be robust against this sort of user error.
J. Betzwieser, B. Bland, J. Kissel
While trying to turn on H2SUSFMY, post-cartridge install, we noticed two problems with the sensor signals coming in from the OSEMs.
(1) On the input side, the raw ADC channels (H2:SUS-FMY_M1_OSEMINF_*_IN1_DQ) were very small, and oscillating around zero (say, 0 +/- 5 cts).
(2) Just after the compensation filters, the signals (H2:SUS-FMY_M1_OSEMINF_*_OUT_DQ) were large (say, 120000 +/- 5 cts).
The first problem turned out to be that the H2SUSFMY Rack electronics were not powered on. Once turned on, we found a different problem: signals were all 100 +/- 2000 cts, where these channels should never go negative. If centered and the suspension is free the signals should be +15000 +/- 1000. This is still under investigation, stay tuned for further results.
The second problem turned out to be a bug in the OSEMINF deWhite, sat amp compensation filters (installed in FM1 of the H2:SUS-FMY_M1_OSEMINF_* filter banks). These filters were installed with the matlab easyquack/automatic compensation filter generator software suite called using,
${SusSVN}/sus/trunk/Common/MatlabTools/prepare.m
some time ago to test out the program (last time I was at LHO, between Nov 13 and Nov 20, 2011; I didn't aLOG it ). Since, we've discovered a bug in the generator that adds a factor ~6 DC gain to these filters, when they should have a DC gain of 1.
Joe is aware of the bug, and currently fixing it, but in the mean time, in the interest of expediency I've just fixed the bug "by hand," editing the filter text file in foton. These fixed filters have been loaded, and the OSEMINF_*_OUT signals appear as expected (baring in mind the first problem is still there).
Once Joe fixes prepare, we'll try running it again (and I'll aLOG it this time!).
There were issues with attempting to engage the ITMY M0 and R0 damping filters. After investigation, the medm filter values for the *COILOUTF_* gains were inconsistent with earlier changes to these gains. The ITMY M0 and R0 damping filters were last engaged on the LVEA SUS Test Stand with these values just before the BSC8 cartridge install. Damping functionality can be confirmed with a live dataviewer session displaying the signal damping. The values have been changed to the following: ITMY M0 COILOUTF_* 01/03/2012 before 01/03/2012 AFTER F1 = -1 F1 = 1 F2 = 1 F2 = 1 F3 = -1 F3 = -1 LF = 1 LF = -1 RT = -1 RT = 1 SD = 1 SD = -1 -------------------------------------------------- ITMY R0 COILOUTF_* 01/03/2012 before 01/03/2012 AFTER F1 = -1 F1 = 1 F2 = -1 F2 = 1 F3 = 1 F3 = -1 LF = -1 LF = 1 RT = 1 RT = -1 SD = 1 SD = -1
I've remotely closed the H2 SUS ITMY M0 and R0 damping loops, and confirmed that they are now functional, as they were when confirmed by Jeff G ! Just to be sure we don't loose this information, I've burt captured two states /opt/rtcds/lho/h2/userapps/release/sus/h2/burtfiles/itmy/ h2susitmy_damped.snap (Damping loops ON) h2susitmy_safe.snap (Damping loops OFF) One thing I'm confused about: the COILOUTF gains shown above are inconsistent with the polarity of the magnets (as per E1000617): COILOUTF Gain Magnet Sign M0 F1 + N M0 F2 + S M0 F3 - N M0 LF - S M0 RT + N M0 SD - S R0 F1 + N R0 F2 + N R0 F3 - S R0 LF + N R0 RT - S R0 SD - S From the chart above, it would be consistent (N == +, S == -), if the M0 F2 and M0 F3 magnet signs were flipped -- either in E1000617, or physically on the suspension. Now -- this raises a flag -- M0 F2 and M0 F3? We had some unresolved cross-coupling between Longitudinal and Yaw drive while the cartridge was still on the mechanical test stand, originally seen in LHO aLOG 1839 and further confirmed in LHO aLOG 1852. If the magnet sign was/is flipped on one of these two sensors and the COILOUTF gains did not properly compensate for them, we would expect to have excess cross-coupling between Yaw and Longitudinal. For now, we have damping loops running, and we will leave the suspension as such, so that the seismic group can press forward. However, in the down-times between the seismic testing suite, and before we close up the chamber, we should (among other planned tests) (1) Retake the low-frequency Y2Y and Y2L transfer functions, to confirm that the cross coupling is still present. (2) If so, we should measure OSEM Basis transfer functions (F2toF2, and F3toF3, and maybe others) and compare. (This should really be a part of our standard testing suite.) (3) If we're still confused, we'll need to take off the F2 anf F3 OSEM sensors and measure the magnet signs.
While discussing with Anamaria about what might be going ON, I drew up two tables to help me better elucidate the problem. I include them here, 'cause they might be useful for broader discussion. If we take the magnet polarity from E1000617 as cannon, then I would expect the M0 face sensors to have the following signal-sign-flip chain (assuming a positive coil current repels a N, and attracts a S magnet) Test OUT E2O Gain COILOUTF Gain Current Out Magnet Pol. Resulting Force Resulting Motion { F1 0 +1 0 N none } + Long---{ F2 + -1 - S Push } -- + Long { F3 + +1 + N Push } { F1 - +1 - N Pull } + Pitch--{ F2 + -1 - S Push } -- + Pitch { F3 + +1 + N Push } { F3 0 +1 0 N none } + Yaw----{ F2 + -1 - S Push } -- + Yaw { F3 - +1 - N Pull } This is how I had set up the COILOUTF gains before today (though I was off by an overall minus sign). However, since Jeff G.'s has re-installed COILOUTF gains as he has shown above, and the damping loops close and are stable, then that implies the following magnet polarity Test OUT E2O Gain COILOUTF Gain Current Out Magnet Pol. Resulting Force Resulting Motion { F1 0 +1 0 N none } + Long---{ F2 + +1 + N Push } -- + Long { F3 + -1 - S Push } { F1 - +1 - N Pull } + Pitch--{ F2 + +1 + N Push }-- + Pitch { F3 + -1 - S Push } { F1 0 +1 0 N none } + Yaw----{ F2 + +1 + N Push } -- + Yaw { F3 - -1 + S Pull } In other words, though the magnet polarities are properly compensated for, it doesn't match E1000617. That means if any other suspensions are assembled to the E1000169 specification, we can't necessarily use these COILOUTF gains. Other thoughts: - Because both of the above arrangements should result in the same motion, I'm lowering my EURIKA! flag a little on the guess that this is the source of the cross-coupling. - It's strange that the cross coupling does not appear in both degrees of from, i.e. Yaw resonances don't show up in the L2L TF, but L resonances show up in Y2Y. I think I may have thought this before which let me down the "it's air currents!" path. Anyways, my path forward outlined above still holds... we need a few more measurements before we start changing hardware -- or close the chamber and "aLIGO accept" the suspension.