Let's assume the additional flat noise in the ~100 Hz region that might be limiting now (w.r.t. to O4a) is due to OMC length noise. Either the OMC lenght noise is larger than before, and coupling through the residual OMC length RMS noise, or the OMC lock has an offset.
Let's assume that the OMC was locked at the top of the resonance (no offset, to be confirmed with the new demodulation phase).
According to 76137, the two PZT responses are PZT1 = 11.3 nm/V, and PZT2 = 12.7 nm/V.
Following Sheila's note in 30510, the normalized OMC transmission (RIN) is given by [after correcting for a mistake in the coefficient multipling F]
RIN = 1 / (1 + (2 F (x0 + dx)/ lambda)^2 )
where F = 400 is the OMC finesse (76386), x0 is a static lock offset (or equivalent RMS fluctuation) and dx is OMC lenght noise (form example due to dither).
The amplitude of the dither line is 0.23 V peak, corresponding to a dither amplitude (peak) of A = 2.6e-9 m, using the PZT1 calibration above.
The locking error signal is obtained using a length modulation dx = A sin(wt) that gives a RIN = (2F/lambda)^2 A sin(wt) x0, where x0 is the offsetf from resonance of the OMC length. Once demodulated, this gives
OMC-LSC_I = (2F/lambda)^2 A/2 x0 = 7.3e8 error_signal_demodulated_RIN / m (note that 30510 seems to be wrong and missing some factors, thank you Elenna for checking)
This allows me to calibrate the OMC-LSC input signal. The RMS with the OMC locked is 4.7e-5 RIN, corresponding to 6.4e-14 m RMS of residual OMC fluctuation around the lock point.
The flat noise in DARM is about 7e-21 m/rHz. Using the optical gain from the calibration measurement (3.4e6 LSC-DARM_IN cts/m) and the ratio LSC-DARM_IN / OMC_DCPD_NORM = 1.6e-5, I find an optical gain of 2.1e11 RIN/m for OMC-DCPD_NORM
Therefore the noise in DARM corresponds to a OMC-DCPD RIN of 1.5e-9 RIN/rHz
Noise coupling due to the residual OMC length RMS goes like (2F/lambda)^2 x_RMS dx_noise, where x_RMS is now the residual RMS motion computed above. Using this conversion, I found that the excess noise in DARM would correspond to a OMC length noise of 4e-14 m/rHz at 100 Hz. This still seems higher than the expected noise that should be in the 3e-16 m/rHz range (see for example section 8 of T1000276)
Tests to do:
In addition to the BSC10 accelerometer, the amount of floor motion also increases over the past 6 weeks, though not in a sudden fashion.
This does not correspond to the time of the most recent fan swap, judging by fan accelerometers.
New EX and EY Accelerometer Power Conditioners were installed 30 January 2024. This is roughly the same time as some of these jumps in the trend. The EY BSC 10 accelerometer cable had a questionable connector but still functioned so I believe we left it, it may need to be replaced.
https://alog.ligo-wa.caltech.edu/aLOG/index.php?callRep=75592
We replaced the loose connector but did not see any effect on the signal. While down there we looked at the output and found that channel 5 output was very noisy, and looking back at the notes in my prior ALOG, channel 5 = PEM EY BSC ACC X and back then it did not register as an accelerometer. I assume this accelerometer is not functional or the cabling is not correct. We plan to go back on Tuesday and track down the issue with this accelerometer and possibly repair the channel in the power conditioner chassis.
Other notes
The INPUT to CH3 on the power conditioner is "TBL-Y" accelerometer cable. When unplugged this affected "BSC-Y" signal plot.
The INPUT to CH4 on the power conditioner is "BSC-Z" accelerometer cable. When unplugged this affected "BSC-Z" signal plot. (this one was correct)
Looking back at my analysis of the drawings in the linked ALOG, the above note matches the drawings in the DCC D1300773. I propose we assume the cables are swapped incorrectly but labeled correctly, and we rearrange the cables to match the drawing.
Marc, Fil, Gerardo, Janos
Refer to LHO:76728.
Naoki, Daniel, Nutsinee
Today we increased RF6 from -22dBm to -13 dBm and 8 dBm. We saw excess noise at 8 dBm above 300Hz but no excess noise at -13dBm. REF 12 is the squeezing at -22dB before we started the test. Using the time from alog76553. REF9 and REF10 both show squeezing at -13dBm RF6 at different squeeze angle where one has a better sensitivity at low frequency bucket. REF13 shows squeezing at 8dBm RF6. The excess noise above 300Hz cannot be improved with squeeze angle. Investigation is required.
We turned off ADF sqz angle servo during the test. We readjusted the ADF squeeze angle demod phase and accepted the new value in the SDF.
We are parking RF6 at -12dBm. Since Daniel didn't like the unlucky number 13.
Loop | Was (-22dBm RF6) | Now (-12 dBm RF6) |
CLF gain | 10 | 0 |
LO gain | -7 | -12 |
FC LSC gain | -2.6 | -0.86 |
FC ASC gain | 0.1 | 0.03 |
The -22dBm, -12dBm, 8dBm RF6 correspond to 9 uW, 28 uW, 420 uW CLF REFL power.
We rechecked the FDS -22dBm time as the time in the above plot wasn't sqz opitmized to the bucket. Can see in attached plot, CLF at -22dBm and -13dBm have the same SQZ in the bucket, as expected.
Looking back at the past data it seems we may not have adjusted the CLF ISS gain properly during the test causing our sqz level to be stuck at 3dB at kHz region. CLF_REFL_DC was oscillating when RF6 was at -13 dBm and at 8 dBm. This looks like an easy fix and we should try again at some point.
Daniel Nutsinee
Reducing the gain didn't seem to fix the oscillation. We cranked up the CLF power so the RF6 read 6dBm and went out to look at the signal on the scope. We saw 60kHz beat note on the OPO refl and a crooked 105kHz sinewave on the CLF refl. We don't know where the 60kHz beat on the OPO refl came from. We couldn't make any improvement by changing the CLF ISS gain.
After some investigation we realized the oscillation disappeared when we unplugged the RLF. The oscillation came back when the RLF was plugged back in. The oscillation associated with the RLF seemed obvious only when we operated at high power. Next time we try high CLF power again we should attenuate the RLF RF output to the AOM.
The funny thing was PMC refl saw this oscillation as well. We hope this was just an electronics cross talk.
For even higher CLF power with +6dBm at the RF6 demod, we set the CLF servo IN2 gain to-18dB (from 0dB), the CLF ISS gain to 0dB (from 17dB), and the ISS input set point to 2.037 (from 0.347).
SDFs from green initial alignment setpoints
Jenne was pecking away at SDFs (separate alogs), Jennie/Evan did OMC (I took screenshot below), Louis helped with PCal.....Squeezer work is currently active, so will wait for that team to ACCEPT Squeezer!
Pecking away at some SDFs in preparation for OBSERVING tonight:
Easy Ones To ACCEPT:
More Involved to ACCEPT:
These changes were accpted, but need to be set again after aligning the FC IR transmission.
Noaki added a gain increase to the CAM1 PIT loop for faster convergence. It should be in the guardian, so I've accepted it in SDF.
DHARD yaw new FM8, alog 76314.
Accepting AS_A offset engagement in Observe.snap. Values from alog 76500
I've accepted dark offsets for the LSC and ASC PDs in SDF for the Observe.snap files.
TITLE: 03/20 Eve Shift: 23:00-07:00 UTC (16:00-00:00 PST), all times posted in UTC
STATE of H1: Commissioning
OUTGOING OPERATOR: Corey
CURRENT ENVIRONMENT:
SEI_ENV state: CALM
Wind: 13mph Gusts, 10mph 5min avg
Primary useism: 0.03 μm/s
Secondary useism: 0.19 μm/s
QUICK SUMMARY:
Engineering Run #16 (ER16) started this morning and Oli handed over an H1 in NLN with Camilla doing a Squeezer measurement and there is a possibility we may try to "squeeze" in a few other measurements (i.e. no squeezing quiet time) before the 6pm target for Observing.
TITLE: 03/20 Day Shift: 15:00-23:00 UTC (08:00-16:00 PST), all times posted in UTC
STATE of H1: Commissioning
INCOMING OPERATOR: Corey
SHIFT SUMMARY: Commissioning all day with a few locklosses. Relocking took an average of 42ish minutes.
LOG:
15:00 Detector got to NOMINAL_LOW_NOISE
19:25 Lockloss
20:38 NOMINAL_LOW_NOISE
20:42 Lockloss in NOMINAL_LOW_NOISE from commissioners
21:31 NOMINAL_LOW_NOISE
Start Time | System | Name | Location | Lazer_Haz | Task | Time End |
---|---|---|---|---|---|---|
15:13 | Elenna | Remote | n | A2L tests | 16:13 | |
17:35 | FAC | Karen | WoodShop | n | Tech clean | 18:20 |
17:51 | FAC | Kim | H2 | n | Tech clean | 18:13 |
17:58 | EE | Fil | EY | n | Check hotspot | 18:25 |
18:25 | EE | Fil | EX | n | Getting other hotspot | 18:47 |
18:34 | SHG | Julian | Optics Lab | y(local) | Working on SHG | 19:46 |
18:43 | FAC | Tyler | Water tower | n | Turning on tractor but not driving it | 19:13 |
19:47 | WLK | Ibrahim | along EY | n | Taking a nice walk | 20:31 |
Naoki, Nutsinee, Camilla
We turned the SQZ_ANG_ADJUST servo back to it's O3a nominal ADJUST_SQZ_ANG_ADF. Changed sqzparams.use_sqz_angle_adjust to True and reloaded SQZ_MANAGER and SQZ_ANG_ADJUST.
Set H1:SQZ-ADF_OMC_TRANS_PHASE as 133deg, new scan (as in 76434) running now to check what angle is best for total squeezing.
Accepted at H1:SQZ-ADF_OMC_TRANS_PHASE = 120. This seems to give us the best range but not high frequency SQZ. Plot attached.
We optimized the sqz angle after high CLF test and readjusted the AADF demod phase.
We should check the ADF offset with a more themalized IFO as the SQZ angle servo seems to have pulled even the yellow BLRM to a worse location, see attached.
Naoki, Camilla, Evan, Sheila, Julian, Nutsinee
Many things happened with the squeezer this afternoon. A quick summary is we are back to 5 dB at kHz and we should be able to do this repeatedly. No PSAMs adjustment required at this time.
- When the IFO relocked this afternoon we adjusted ZM5 alignment to optimize ADF trans signal. By doing so we improved both the RF3 and the 42. However this made squeezing worse.
- We adjusted the SQZ angle. We couldn't make it better so we went the other way. This made squeezing worse and ADS TRANS went up with it. Note that this is the IQSUM channel. We didn't think that was a sensible behavior but we've seen it before.
- Sheila and Julian then optimized the crystal tempeature. The NLG for today was 17.3.
- Naoki measured the SQZ IFO sensing matrix. We found a big cross coupling between ZM5 P to AS42 B Y. Other than then everything else was sensible. A new improved sensing matrix has been implemented.
- We lost hours tracking down why the filter cavity failed to lock on green. A reminder to check SDF next time we run into mysterious problems.
- After everything went back to normal we recovered 5 dB of squeezing. DARM plot said so. BLRMS seemed slightly off. We tried turning the ASC loop off and optimizing the ZM alignment by hand to see if we could do any better than the loop. We couldn't. SQZ IFO ASC loop now works as it should.
- We also optimized the filter cavity offset. Mostly to double checked that we were sitting at a good place. An offset of -28 (where we started) gave the best squeezing at low frequency.
We haven't got to increase CLF power today.
After a new CLF VCO installed we should revert the CLF sign to make sure everything was the same as before. In theory this shouldn't do anything.
Naoki Nutsinee
We changed "fcgs_trans_lock_threshold" to 120 today so FC wouldn't lock on higher order mode. The filter cavity was having trouble getting pass GR VCO lock so we have now reduced this power back to 80.
Accepted the new ASC_INMATRIX settings in sdf, see attached. Aslo accepted ASC_POS_Y's new minus sign and AS_A_RF42_YAW_OFFSET.
Accpeted the SQZ_ASC WFS as OFF. As decided, we will start the ER with SQZ ASC IFO off.