Reports until 00:03, Sunday 15 October 2023
H1 General
oli.patane@LIGO.ORG - posted 00:03, Sunday 15 October 2023 (73470)
Ops EVE Shift End

TITLE: 10/15 Eve Shift: 23:00-07:00 UTC (16:00-00:00 PST), all times posted in UTC
STATE of H1: Earthquake
INCOMING OPERATOR: Corey
SHIFT SUMMARY: Second half of my shift had a lot of ground motion and a lockloss. We are now in NOMINAL_LOW_NOISE and just waiting for the camera servos before getting into Observing.
LOG:

23:00UTC Detector Observing and has been Locked for 35.5hours

03:54 Earthquake mode activated due to local ground motion
04:14 Back to CALM
04:14 Earthquake mode activated due to incoming earthquake from Afghanistan

04:25 DIAG_MAIN message: SERVO_BOARDS: IMC-REFL_SERVO_SPLITMON > 8V
04:30-04:38 SERVO_BOARDS: IMC-REFL_SERVO_SPLITMON > 8V message occurring more frequently
04:37-04:38 SRM saturations every few seconds

04:38 Lockloss after 41hours (73466)
04:58 Starting INITIAL_ALIGNMENT

05:36 Back to CALM

05:46 Earthquake mode activated due to local earthquake
05:56 Back to CALM

06:01 Lost lock at CHECK_AS_SHUTTERS

06:53 Reached NOMINAL_LOW_NOISE

H1 General (Lockloss)
oli.patane@LIGO.ORG - posted 23:08, Saturday 14 October 2023 - last comment - 23:59, Saturday 14 October 2023(73466)
Lockloss

Lockloss @ 10/15 04:38UTC

We were staying locked through an earthquake but got the DIAG_MAIN message: SERVO_BOARDS: IMC-REFL_SERVO_SPLITMON > 8V at 04:25 and then multiple times and more often in the last few minutes. SRM was constantly saturated in the last minute of the lock. T1 is where DARM_IN1 gave out.

Because ground motion is still very high and we will need to do an initial alignment, I'll be holding us in DOWN for at least ~10mins

 

Images attached to this report
Comments related to this report
oli.patane@LIGO.ORG - 21:59, Saturday 14 October 2023 (73467)

04:58 Attempting an Initial Alignment

oli.patane@LIGO.ORG - 23:02, Saturday 14 October 2023 (73468)

06:01UTC Lost lock at CHECK_AS_SHUTTERS

oli.patane@LIGO.ORG - 23:59, Saturday 14 October 2023 (73469)

06:53 Reached NOMINAL_LOW_NOISE

H1 General
oli.patane@LIGO.ORG - posted 20:42, Saturday 14 October 2023 (73465)
Ops EVE Midshift Update

We've been Locked for 40 hours now and are Observing at 155Mpc

Quiet night so far. useism is trending up but isn't too bad. Wind has gone up to ~15mph in the last half hour.

H1 General
oli.patane@LIGO.ORG - posted 16:04, Saturday 14 October 2023 (73464)
Ops EVE Shift Start

TITLE: 10/14 Eve Shift: 23:00-07:00 UTC (16:00-00:00 PST), all times posted in UTC
STATE of H1: Observing at 161Mpc
OUTGOING OPERATOR: Ryan C
CURRENT ENVIRONMENT:
    SEI_ENV state: CALM
    Wind: 5mph Gusts, 4mph 5min avg
    Primary useism: 0.05 μm/s
    Secondary useism: 0.29 μm/s
QUICK SUMMARY:

In Observing and Locked for 35.5 hours! Everything looking good!

H1 General
ryan.crouch@LIGO.ORG - posted 16:00, Saturday 14 October 2023 (73463)
OPS Saturday day shift summary

TITLE: 10/14 Day Shift: 15:00-23:00 UTC (08:00-16:00 PST), all times posted in UTC
STATE of H1: Observing at 161Mpc
INCOMING OPERATOR: Oli
SHIFT SUMMARY: The microseism is still rising, winds been very low today, we've been locked for 35:27 as of 23:00UTC.

We dropped observing briefly from me miss clicking something from 18:56:29 - 18:56:47 UTC.

LOG:

No log

H1 General
ryan.crouch@LIGO.ORG - posted 12:12, Saturday 14 October 2023 (73462)
OPS Saturday day shift midshift update

We dropped observing briefly from me miss clicking something from 18:56:29 - 18:56:47 UTC.

We've been locked for 31:40, everything looks stable, saturday tours ongoing.

LHO VE
david.barker@LIGO.ORG - posted 10:52, Saturday 14 October 2023 (73461)
Sat CP1 Fill

Sat Oct 14 10:05:05 2023 INFO: Fill completed in 5min 1secs

A quick fill, LLCV had just ramped to 100% open.

Images attached to this report
H1 General
ryan.crouch@LIGO.ORG - posted 07:56, Saturday 14 October 2023 (73460)
OPS Saturday day shift start

TITLE: 10/14 Day Shift: 15:00-23:00 UTC (08:00-16:00 PST), all times posted in UTC
STATE of H1: Observing at 163Mpc
OUTGOING OPERATOR: Corey
CURRENT ENVIRONMENT:
    SEI_ENV state: CALM
    Wind: 4mph Gusts, 3mph 5min avg
    Primary useism: 0.05 μm/s
    Secondary useism: 0.26 μm/s
QUICK SUMMARY:

H1 General
oli.patane@LIGO.ORG - posted 00:05, Saturday 14 October 2023 (73459)
Ops EVE Shift End

TITLE: 10/14 Eve Shift: 23:00-07:00 UTC (16:00-00:00 PST), all times posted in UTC
STATE of H1: Observing at 163Mpc
INCOMING OPERATOR: Corey
SHIFT SUMMARY: We have now been Locked for 19.5hours. PSL ISS % diff is low, around 1.9%. Uneventful evening overall, but there is an earthquake from New Zealand heading in soon. The ring heater changes that Camilla made (73445) are still okay and we will hopefully continue to not have any issues with them. I didn't notice any issues with the ETMY coildriver(73442) pop up either.
LOG:

23:00UTC Detector Observing and has been Locked for 11.5 hours

02:28 Earthquake mode activated without warning due to sudden spike in ground motion
02:38 Back to CALM

H1 General
oli.patane@LIGO.ORG - posted 20:11, Friday 13 October 2023 (73458)
Ops EVE Midshift Update

Observing at 158Mpc

Calm evening and have now been locked for 15hrs 40mins. We entered Earthquake mode from 10/14 02:28-02:38 UTC due to a small local earthquake, but managed to stay locked.

LHO FMCS (PEM)
oli.patane@LIGO.ORG - posted 20:01, Friday 13 October 2023 (73457)
HVAC Fan Vibrometers Check

Closes FAMIS#26257, last checked 73321

Corner Station Fans (attachment1)
All fans are looking normal and within range.

Outbuilding Fans (attachment2)
All fans are looking normal and within range.

Images attached to this report
H1 SQZ
dorotea.macri@LIGO.ORG - posted 17:58, Friday 13 October 2023 - last comment - 12:31, Monday 16 October 2023(73456)
OPO green trans/refl power trend over the past year

[Vicky, Regina, Dorotea, Sheila]

The attached plot shows the ratio of green light transmitted vs reflected through the OPO over the past year to see how green OPO cavity losses have changed.

We last moved the OPO crystal in Nov. 2022 (see relevant alog). Shortly after moving the crystal, the ratio was around 5% and degraded to around 4% within the first week; it has since settled between 2-3% for most of the past year.

We think the discontinuity around 23/04/16 was due to rejecting power away from the refl PD, which was done around that time because the PD was being saturated. If we look at the refl power alone we can see clear saturation occurring on the PD in the time before the power was lowered. We think the loss curve would be fairly continuous if not for the saturation, but can't exactly compensate since we don't know how much power is being lost. The plot shows only times from when the detector was "stable", but stability was calculated fairly naively, leading to some outlier points remaining from when the detector wasn't actually locked; however, the general trend seems pretty consistent.

Images attached to this report
Comments related to this report
victoriaa.xu@LIGO.ORG - 12:31, Monday 16 October 2023 (73502)

History of crystal movements before O4, after HAM7 installation. Compared to ~1000+ steps between crystal co-resonances, the opo crystal has not really moved to a different co-resonance position since installation.

  • Aug 2, 2022, LHO:64272: -300 steps "right", +200 steps "left". Total -100 steps "right", within error of translation stage hysteresis.
  • Nov 9, 2022, LHO:65684: +160 steps "left", -300 steps "right", +100 counts "left". Total -40 steps "right", within error of hysteresis.

Estimating spots between crystal co-resonances: From e.g. Maggie's MIT/Lasti ilog and LLO crystal scans (e.g. LLO:49568 one side to other side of crystal was from (+3,180 and -11,820) counts, for either LLO:53429 10 co-resonance spots, or LLO:60710 13 co-resonance spots), it seems to average about (15000/13) ~ 1150 steps between fixed-temperature crystal co-resonances, save for the fine-tuning needed at each position. Compared to this ~1150 steps between crystal spots, our previous moves have basically been circling one spot.

H1 SQZ
regina.lee@LIGO.ORG - posted 16:57, Friday 13 October 2023 (73454)
Trending OPO IR Trans to Refl Ratio Over the Past Year
[Vicky, Regina, Dorotea, Sheila]
We looked at the IR seed light transmitted vs reflected ratio through the OPO to see if any losses can be inferred by this ratio degrading through this past year. We're also unable to probe the IR losses in real time so we trended back over a year and grabbed data points (plot here). Dorotea's follow up post will look at green losses in the OPO cavity which are easier to see since green light enters the OPO cavity through M1 with R1_532 ~98%. This log is trying to look at red OPO losses (which are squeeze losses in the form of degrading OPO escape efficiencies). But this measurement is effectively injecting IR light at M2, which is highly reflective at R2_1064 ~99.9%, so losses will look like a slight change in this trans/refl ratio, which is already very small. 
 
Our measurements do not rule out that we're seeing loss, but it's hard to infer it from this measurement alone. We probably don't have enough consistent data points to see the trend of the transmission vs reflectance ratio over time. 
 
Related alogs of on-table measurements of the trans/refl ratio through the OPO:
Images attached to this report
H1 General
ryan.crouch@LIGO.ORG - posted 16:02, Friday 13 October 2023 (73442)
OPS Friday day shift summary

TITLE: 10/13 Day Shift: 15:00-23:00 UTC (08:00-16:00 PST), all times posted in UTC
STATE of H1: Observing at 160Mpc
INCOMING OPERATOR: Oli
SHIFT SUMMARY: We've been locked all shift, 11:30 as of 23:00

Diag_main has been flashing with "ISS diffracted power is low" message every 10-15 minutes.

LOG:                                                                                                                                                                                                        

Start Time System Name Location Lazer_Haz Task Time End
16:06 PEM Robert LVEA, CER, CR N PEM tests/injections 17:56
18:26 VAC Gerardo FCES N Bring some equipment down, He sprayer 19:04
19:10 FAC Tyler EndY N Check chillers are working 21:28
19:15   Camilla, Jeff MidX N Running down the arm 19:46
19:53 VAC Travis Mids N Check out pumps, part compatibility? 20:08
20:29 FAC Randy EndX->MidX N Move boxes 21:12
Images attached to this report
H1 General
oli.patane@LIGO.ORG - posted 15:56, Friday 13 October 2023 (73453)
Ops EVE Shift Start

TITLE: 10/13 Eve Shift: 23:00-07:00 UTC (16:00-00:00 PST), all times posted in UTC
STATE of H1: Observing at 162Mpc
OUTGOING OPERATOR: Ryan C
CURRENT ENVIRONMENT:
    SEI_ENV state: CALM
    Wind: 8mph Gusts, 6mph 5min avg
    Primary useism: 0.03 μm/s
    Secondary useism: 0.18 μm/s
QUICK SUMMARY:

Detector is Observing and has been Locked for 11.5 hours. Dust monitors are all good and wind and useism are low.

H1 SUS (OpsInfo)
thomas.shaffer@LIGO.ORG - posted 15:48, Friday 13 October 2023 - last comment - 11:06, Thursday 19 October 2023(73452)
Started making a DARM BLRMS monitor for violin modes

In order to more easily track and notify on rising violin modes, I've started making a DARM BLRMS monitor around 490-520Hz. This is currently in position #8 in place of Camilla 6600-6800Hz that didn't give expected results (alog73272). It looks like its working, but not the best it could be. Jenne gave me some pointers that I'll try at another time to get this to better show us the violin mode total magnitude. Once it's looking acceptable I'll make others for the harmonics as well.

Images attached to this report
Comments related to this report
thomas.shaffer@LIGO.ORG - 11:06, Thursday 19 October 2023 (73591)

Added some more notches for the other harmonics and upped the attenuation on the bandpass. I also took over slot #9 for the 1k violin modes. I think they are working somewhat well, but I'd really like to watch this next time we have a violin mode ring up to see if it's accurate.

Images attached to this comment
H1 TCS
camilla.compton@LIGO.ORG - posted 12:04, Friday 13 October 2023 - last comment - 11:51, Thursday 09 November 2023(73445)
ETM RHs turned up 0.1W at 19:03UTC.

Both ETM RH turned up from 1.0W to 1.1W/segment at 19:03UTC, plan to increase another 0.1W later this afternoon. Follow on from 73437. Will stay in observing during this test.

Comments related to this report
camilla.compton@LIGO.ORG - 14:07, Friday 13 October 2023 (73450)

Made another step up of +0.1W to 1.2W/Segment on ETMX and ETMY at 21:07UTC.

camilla.compton@LIGO.ORG - 16:26, Friday 13 October 2023 (73451)DetChar, ISC, OpsInfo

Plots attached of HOM, DARM and ndscopes. Jenne pointed out we should use GDS-CALIB for DARM as it isn't effected bt the calibration changing with the RH changes. On ndscopes, not that at -4hours theres a step in SQZ that effects the range 73446.

High frequency noise reduce, DARM maybe better in in the bucket but circulating power down 7kW and Kappa_C down 0.8%.

This doesn't seem to be doing anything bad to the range so we can leave the ETM Ring Heaters in this 1.2W setting for the weekend. If Operators have any troubles, they can reduce H1:TCS-{ETMY,ETMY}_RH_SET{UPPER,LOWER}POWER from 1.2W to 1.0W.

Images attached to this comment
camilla.compton@LIGO.ORG - 11:30, Monday 16 October 2023 (73499)

Adding plots of 11:00UTC,13h30 after ETM RH change. DARM ~1000Hz looks like it thermalized worse than 2 hours after the RH change. 6kHz DARM continued to reduce, but it started that lock particularly high.  Circulating power settled at 367kW, 7kW less than nominal. KAPPA_C dropped nearly 1%.

Images attached to this comment
camilla.compton@LIGO.ORG - 11:51, Thursday 09 November 2023 (74116)

These RH changes were reverted 16 October 2023 73503.

Displaying reports 17221-17240 of 88545.Go to page Start 858 859 860 861 862 863 864 865 866 End