TCSY Y Chiller Settings Settings Units Temperature C Pressure psi Flow gpm Setpoint 17.8 C Temperature High Fault 25.0 C High Warning 24.0 C Low Warning 16.0 C Low Fault 15.0 C Pressure High Fault 105.0 psi High Warning 100.0 psi Low Warning 4.0 psi Low Fault 3.0 psi High P Delay 0 sec Low P Delay 10 sec Fluid Level Low Warning 6.0% Low Fault 0.0% Flow High Fault 0.0 gpm High Warning 0.0 gpm Low Warning 0.0 gpm Low Fault 0.0 gpm Auto Restart F Audible Alarms T Care Level 1 Serial Comm - DCOM Serial Type Off Analog Comm - ACOM Remote Sensor F Remote Start F Remote Setpt volts Temp Out F RELAY 1 Low Level T Tank Overflow F Drip Pan Full F Low Temp T High Temp T Low Flow T High Flow F Low Resistivity F High Resisitivity F High Pressure T Low Pressure T Unit Fault F Pump/unit Shut Off F Refrigerator Shut Off F Sensor Fault F RELAY 2 Low Level F Tank Overflow F Drip Pan Full F Auto Refill Error F Low Temp T High Temp T Low Flow F High Flow F Low Resistivity F High Resistivity T High Pressure F Low Pressure F PM Timer F Comm Error F Sensor Fault F User Range Settings Voltage High Volts 10.0 Low Volts 0.0 High Temp 40.0 Low Temp 5.0 Millivolt High mv 1000.0 Low mv 0 High Temp 100 Low Temp 0 Current High ma 20.0 Low ma 4.0 High Temp 40.0 Low Temp 5.0 Show Quick Start F Tuning Cool PID P 10.0 I 0.50 D 0.00