Displaying report 1-1 of 1.
Reports until 16:44, Wednesday 05 September 2012
H2 CDS
keita.kawabe@LIGO.ORG - posted 16:44, Wednesday 05 September 2012 - last comment - 13:57, Thursday 06 September 2012(4099)
Foton bug bites seriously

Foton GUI quietly discarded (some of?) notch filter definitions and replaced them with a flat gain of 1.

This is easily reproduced by first opening e.g. /opt/rtcds/lho/h2/chans/filter_archive/h2iscey/H2ISCEY_120828_143926.txt and saving it to some other file, e.g. test.txt, and take a diff (attached).

Probably because of this bug, all WFS notches are gone from current H2ISCEY filter file.

This is extremely worrisome.

Non-image files attached to this report
Comments related to this report
keita.kawabe@LIGO.ORG - 13:57, Thursday 06 September 2012 (4114)

It's not notches, it's zero ramp time.

 

bugzilla report of this:

https://bugzilla.ligo-wa.caltech.edu/bugzilla/show_bug.cgi?id=414

 

Jim Batch already found the cause of this (ramp time was zero for the filter), and is working on a future workaround. In the mean time, if you select "ramp" switching, don't forget to set the ramp time manually to something non-zero.